All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

P

OWER SUPPLY

1AC 24V 90W

AC 100-240V Wide-range input

Cost optimized without compromising quality or
reliability

No PE connection required

Width only 36mm

Efficiency up to 93.8%

Low no-load power losses

Full power between -10°C and +60°C

Push-in terminals

3 Year warranty

P

RODUCT DESCRIPTION

S

HORT-FORM DATA

The  PIM90.241  is  a  DIN  rail  mountable  single-phase-
input  power  supply,  which  provides  a  floating,

 

stabilized  and  galvanically  separated  SELV/PELV/ES1

 

output voltage.

The device is equipped with 

p

ush-in terminals, which

 

are optimized for automated wiring.

The  mechanically  robust  housing  is  made  of  a  high-
grade,  reinforced  molded  material,  which  permits

 

surrounding temperatures up to +70°C.

The unit is designed as “Class of Protection” II unit and

 

fulfills  the  safety  and  EMC  requirements  without  an

 

input PE connection. This saves wiring costs.

The PIANO family is a compact industrial grade DIN rail

 

power  supply  series  that  focuses  on  the  essential

 

features needed in today’s industrial applications. The

 

excellent cost/performance ratio does not compromise

 

quality or reliability.

Output voltage

DC 24V

Nominal

Adjustment range 24-28V

Factory setting 24.1V

Output current

3.8-3.2A

Below +60°C ambient

2.8-2.4A

At +70°C ambient

Derate b60°C and +70°C

Input voltage AC

AC 100-240V

±

 10%

Mains frequency

50-60Hz

±

6%

Input current AC

1.45 / 0.95A

At 120 / 230Vac

Power factor

0.58 / 0.45

At 120 / 230Vac

Input inrush
current

18 / 40A

peak

At 120 / 230Vac, +40°C,
cold start

Efficiency

92.1 / 93.8%

At 120 / 230Vac

Power losses

7.9 / 6W

At 120 / 230Vac

Hold-up time

25 / 119ms

At 120 / 230Vac

Temperature
range

-10°C to +70°C

Size (w x h x d)

36x90x91mm

Without DIN rail

Weight

270g / 0.6lb

O

RDER NUMBERS

M

AIN APPROVALS

Description:

Power supply PIM90.241-xx

Order Number:
PIM90.241

For details and the complete approval list, see chapter 18.

Ind. Cont. Eq.

Summary of Contents for PIM90.241

Page 1: ...Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO family is a compact industrial grade DIN rail power supply se...

Page 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Page 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Page 4: ...g 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 69A 1 45A 0 95A At 24V 3 8A see...

Page 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 14A 18A 40A At 40 C ambient...

Page 6: ...unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 3 8A static value see Fig 6 1 Ripple and noise voltage max 100mVpp Bandwidth 20Hz to 20MHz 50Ohm Output curr...

Page 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Page 8: ...3W 0 3W 0 4W At no load typ 5W 4 3W 3 8W At 24V 1 9A half load typ 9 5W 7 9W 6W At 24V 3 8A full load The average efficiency is an assumption for a typical application where the device is loaded with...

Page 9: ...1 9A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representation...

Page 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Page 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Page 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Page 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Page 14: ...ins IT mains typ 130 A 270 A At 230Vac 50Hz TN TT mains IT mains max 80 A 190 A At 110Vac 50Hz TN TT mains IT mains max 120 A 270 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current ma...

Page 15: ...witch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Du...

Page 16: ...rail height must be added to the unit depth to calculate the total required installation depth Weight 270g 0 6lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 1...

Page 17: ...ANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phase...