PIM90.241

Feb. 2022 / Rev. 2.0 DS-PIM90.241-EN

www.pulspower.com

15 / 17

All parameters are specified at 24V, 3.8A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

18. Approved, Fulfilled or Tested Standards

IEC 61010

CB Scheme Certificate
IEC 61010-2-201 - Electrical Equipment for Measurement, Control and
Laboratory Use - Particular requirements for control equipment

IEC 62368

CB Scheme Certificate
IEC 62368-1 - Audio/video, information and communication
technology equipment - Safety requirements
Output safety level: ES1

UL 61010

UL Certificate
Listed equipment for category NMTR - UL 61010-2-201 - Electrical
equipment for measurement, control and laboratory use - Particular
requirements for control equipment
Applicable for US and Canada 
E-File: E198865

IEC 61558-2-16
(Annex BB)

Safety Isolating

Transformer

Test Certificate
IEC 61558-2-16 - Safety of transformers, reactors, power supply units
and similar products for supply voltages up to 1100V 
Particular requirements and tests for switch mode power supply units
and transformers for switch mode power supply units

ISA-71.04-1985

Manufacturer's Declaration (Online Document)
Airborne Contaminants Corrosion Test
Severity Level: G3 Harsh
H2S: 100ppb
NOx: 1250ppb 
Cl2: 20ppb
SO2: 300ppb 
Test Duration: 3 weeks, which simulates a service life of at least 10
years

VDMA 24364

Paint Wetting Impairment Substances Test (or LABS-Test)
Tested for Zone 2 and Test Class C1 according to VDMA 24364-C1-L/W
for solvents and water-based paints

19. Regulatory Product Compliance

EU Declaration of
Conformity

The CE mark indicates conformance with the European

– EMC directive
– Low-voltage directive (LVD)
– RoHS directive

REACH Regulation

Manufacturer's Declaration
EU Regulation regarding the Registration, Evaluation, Authorization
and Restriction of Chemicals
EU Regulation 1907/2006

WEEE Regulation

Manufacturer's Declaration
EU Directive on Waste Electrical and Electronic Equipment Registered
in Germany as business to business (B2B) products.
EU Directive 2012/19/EU

RoHS (China RoHS 2)

Manufacturer's Statement
Administrative Measures for the Restriction of the Use of Hazardous
Substances in Electrical and Electronic Products 25 years

EAC TR Registration

EAC Certificate
EAC EurAsian Conformity - Registration Russia, 
Kazakhstan and Belarus
 8504408200, 8504409000

Summary of Contents for PIM90.241

Page 1: ...Class of Protection II unit and fulfills the safety and EMC requirements without an input PE connection This saves wiring costs The PIANO family is a compact industrial grade DIN rail power supply se...

Page 2: ...ntly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document available under www pulspower com No part of this do...

Page 3: ...ith the input terminals on the bottom of the device Make sure that the wiring is correct by following all local and national codes Use appropriate copper cables that are designed for a minimum operati...

Page 4: ...g 3 1 Shut down voltage typ 54Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 AC 100V AC 120V AC 230V Input current typ 1 69A 1 45A 0 95A At 24V 3 8A see...

Page 5: ...mpact on the inrush current value The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch on AC 100V AC 120V AC 230V typ 14A 18A 40A At 40 C ambient...

Page 6: ...unit Line regulation max 10mV Between 90 and 300Vac Load regulation max 100mV Between 0 and 3 8A static value see Fig 6 1 Ripple and noise voltage max 100mVpp Bandwidth 20Hz to 20MHz 50Ohm Output curr...

Page 7: ...oltage remains within specification following the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The green DC OK LED is also on...

Page 8: ...3W 0 3W 0 4W At no load typ 5W 4 3W 3 8W At 24V 1 9A half load typ 9 5W 7 9W 6W At 24V 3 8A full load The average efficiency is an assumption for a typical application where the device is loaded with...

Page 9: ...1 9A and 25 C 10 MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical representation...

Page 10: ...11 1 Functional diagram 12 Terminals And Wiring The terminals are IP20 Finger safe constructed and suitable for field and factory wiring All Terminals Type Push in terminals Solid wire max 2 5mm2 Stra...

Page 11: ...se noted 13 Front Side And User Elements A Input Terminals N Neutral conductor input L Phase Line input B OutputTerminals Dual terminals for the negative and positive pole Both poles are internally co...

Page 12: ...iterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Voltage dips EN 61000 4 11 0 of 100Vac 0Vac 20ms Criterion A C 40 of 100Vac 40Vac 200ms Criterion C 70 of 100Vac 70Vac 500ms Cri...

Page 13: ...the derated current limits in order not to overload the unit Humidity 5 to 95 r h According to IEC 60068 2 30 No condensation allowed Atmospheric pressure 110 54kPa See Fig 15 2 for details Altitude...

Page 14: ...ins IT mains typ 130 A 270 A At 230Vac 50Hz TN TT mains IT mains max 80 A 190 A At 110Vac 50Hz TN TT mains IT mains max 120 A 270 A At 132Vac 60Hz TN TT mains IT mains Touch current leakage current ma...

Page 15: ...witch mode power supply units ISA 71 04 1985 Manufacturer s Declaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Du...

Page 16: ...rail height must be added to the unit depth to calculate the total required installation depth Weight 270g 0 6lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 1...

Page 17: ...ANCY Do not use this device to build redundant systems since there is no monitoring DC OK signal included 21 5 TWO PHASE OPERATION The power supply can also be operated on two phases of a three phase...

Reviews: