24.3.
Events
This information is triggered by certain situations and will result in an event notification to the IO-Link master. Typical events are notification in case of ideal (e.g. DC-OK) and non-
ideal situations (e.g. ambient temperature too hot, high input voltage etc.).
Events
Event-code
Event-type
Description
Parameter error – Check data sheet and values
0x6320
Error
Device temperature over-run – Clear source of heat
0x4210
Warning
Events. DC-Warning
0x1800
Warning
Output voltage dips more than 10% below adjusted output voltage
Events. Bonus Power
0x1801
Notification
Output current is 5% more than maximum for more than 3s
Events. Over Load
0x1802
Warning
Load higher than allowed
Events. High Voltage Input
0x1803
Warning
Input to high
Events. Low Voltage Input
0x1804
Warning
Input to low
Events. Power Supply down
0x1805
Warning
No link from IO-Link Transceiver to Power Supply
Events. Predictive Maintenance Power Supply
0x1806
Warning
The estimated remaining lifetime has reached 10%. Performance of PSU might be
limited due to aging effects of components.
Events. PSU setting changed via HMI
0x1809
Notification
A PSU setting was changed via man-machine interface.
Events. PSU hardware failure
0x1825
Warning
Critical PSU hardware failure detected. PSU shut down.
Events. PSU output current pre-alarm
0x1830
Warning
Total PSU output current exceeds pre-alarm limit
Events. E-Fuse CH1 Tripped
0x1840
Warning
E-Fuse Ch1 tripped due to overcurrent
Events. E-Fuse CH2 Tripped
0x1841
Warning
E-Fuse Ch2 tripped due to overcurrent
Events. E-Fuse CH3 Tripped
0x1842
Warning
E-Fuse Ch3 tripped due to overcurrent
Events. Output current pre-alarm CH1
0x1850
Notification
Output current on E-Fuse Ch1 exceeds pre-alarm limit
Events. Output current pre-alarm CH2
0x1851
Notification
Output current on E-Fuse Ch2 exceeds pre-alarm limit
Events. Output current pre-alarm CH3
0x1852
Notification
Output current on E-Fuse Ch3 exceeds pre-alarm limit