FPS300.246-036-104
FPS300.246-049-102
All parameters are specified at 24 V, 20 A, 400 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
37 / 43
24.2.
Acyclic data
The parameter values can be accessed to read out additional data (e.g. current output voltage, temperatures etc.), but in addition some of these values can also be written by the
user to configure the power supply (e.g. output voltage and remote on/off).
Parameter
Para.
Index
Sub-
index
Data
type
Bit
offset
Data
Format
Resolution Default
values
Read [R]
Write [W]
Allowed values
Description
Output Voltage Setpoint
105
0
uint16
15-0
Q8.8
2
-8
V/bit
6272
(24.5V)
R/W
6144…7168
Output Voltage Setpoint
Minimum value is 24.0V
Maximum value is 28.0V
Standby
101
0
bool
0
R/W
0 = PSU normal operation (default
value)
1 = PSU standby
Dynamic, excluded from data storage
Configuration Setting
103
0
uint8
7-0
2
R/W
0 = human-machine interface only
1 = IO-Link only
2 = both (default value)
3 = none (button lock)
Dynamic
E-Fuse Channel on/off
106
0
bool array
8-bit Record
1
R/W
0 = off
1 = on
Dynamic
Bit 3…7 not used
Access via subindex 0 only
Chanel 1
0
Chanel 2
1
Chanel 3
2
E-Fuse trip value all CH
108
0
uint16 array 47-0
Q8.8
2
-8
A/bit
max
R
256…2560 at 10A | 256…3072 at 12A
Dynamic
Default is max. current available
E-Fuse trip value CH1
1
uint16
47-32
Q8.8
2
-8
A/bit
max
R
256…2560 at 10A | 256…3072 at 12A
E-Fuse trip value CH2
2
uint16
31-16
Q8.8
2
-8
A/bit
max
R
256…2560 at 10A | 256…3072 at 12A
E-Fuse trip value CH3
3
uint16
15-0
Q8.8
2
-8
A/bit
max
R
256…2560 at 10A | 256…3072 at 12A
E-Fuse Pre-alarm level all CHs
109
0
uint8 array 23-0
Q9.7
2
-7
/bit
103 (80%) R/W
13…192 (10% -150%)
Dynamic
E-Fuse Pre-alarm level CH1
1
uint8
23-16
Q9.7
2
-7
/bit
103 (80%) R/W
13…192 (10% -150%)
E-Fuse Pre-alarm level CH2
2
uint8
15-8
Q9.7
2
-7
/bit
103 (80%) R/W
13…192 (10% -150%)
E-Fuse Pre-alarm level CH3
3
uint8
7-0
Q9.7
2
-7
/bit
103 (80%) R/W
13…192 (10% -150%)
PSU total output current
Pre-alarm level
104
0
uint16
15-0
Q8.8
2
-8
A/bit
5120 (20A) R/W
256…25600 (1A-100A)
Dynamic
EEPROM Status
64
0
uint8
7-0
R
0 = ok
1 = recoverable error detected
2 = unrecoverable error
Dynamic