FPS300.246-036-104
FPS300.246-049-102
All parameters are specified at 24 V, 20 A, 400 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
39 / 43
Parameter
Para.
Index
Sub-
index
Data
type
Bit
offset
Data
Format
Resolution Default
values
Read [R]
Write [W]
Allowed values
Description
Temperature secondary inside 69
0
int16
15-0
Q9.7
2
-7
°C/bit
R
-5120…32640
Temperature secondary inside PSU -40 .. 150°C
Max. temperature secondary
inside
70
0
int16
15-0
Q9.7
2
-7
°C/bit
R
-5120…32640
Maximum temperature secondary inside PSU -40 ..
150°C
Temperature primary inside
71
0
int16
15-0
Q9.7
2
-7
°C/bit
R
-5120…32640
Temperature primary inside -40 .. 150°C
Max. temperature primary
inside
72
0
int16
15-0
Q9.7
2
-7
°C/bit
R
-5120…32640
Maximum temperature primary inside -40 .. 150°C
AC Input Voltage RMS
78
0
uint16
15-0
Q12.4
2
-4
V/bit
R
0…24000 (0-1500V)
Actual Input Voltage RMS (phase-phase)
Actual output voltage
79
0
uint16
15-0
Q8.8
2
-8
V/bit
R
0…12544 (0-49V)
Actual average output voltage
Actual output current
81
0
uint16
15-0
Q8.8
2
-8
V/bit
R
0…12800 (0-50V)
Actual average output current
E-Fuse current all CHs
84
0
Unit16 array 47-0
Q8.8
2
-8
A/bit
R
0…12800 (0-50A)
Actual average E-Fuse current all CH
E-Fuse current CH1
1
uint16
47-32
Q8.8
2
-8
A/bit
0…12800 (0-50A)
Actual average E-Fuse current CH1
E-Fuse current CH2
2
uint16
31-16
Q8.8
2
-8
A/bit
0…12800 (0-50A)
Actual average E-Fuse current CH2
E-Fuse current CH3
3
uint16
16-0
Q8.8
2
-8
A/bit
0…12800 (0-50A)
Actual average E-Fuse current CH3
E-Fuse output status
85
0
Array of bool
8-bit Record
R
0…off
1…on
Dynamic
Bit 3…7 not used
Access via subindex 0 only
Channel 1
0
Channel 2
1
Channel 3
2
E-Fuse trip status CH1
E-Fuse trip status CH2
E-Fuse trip status CH3
86
0
4-bit enum
array
3-0
7-4
11-8
R
0 = No trip
1 = Over-load trip
2 = Short circuit trip
3 = Temperature trip
4 = Power budget trip
5 = Installation failure trip
6 = Sensor fault trip
7 = Fatal fault trip
Dynamic
Bit 12…15 not used
Access via subindex 0 only
Stress level
66
0
uint8
7-0
R
0 … “<=5%”
1 … “>5%”
2 … “>=25%”
3 … “>=50%”
4 … “>=75%”
current load