FPS300.246-036-104
FPS300.246-049-102
All parameters are specified at 24 V, 20 A, 400 Vac, 25 °C ambient and after a 5 minutes run-in time unless otherwise noted.
Apr. 2022 / Rev. 0.2 FPS300-EN
35 / 43
IO-Link Data Types and Description
24.1.
Cyclic Data
The first dataset is called process data and refers to data that is periodically sent to the IO-Link master. The data is updated and communicated every 2ms. All other data in the
power supply itself is generated every 50ms and stored in the IO-Link registers. The higher cycle frequency enables operation with IO-Link masters and attached PLCs without
configuration.
Process
Sub-index
Bit offset
Data type
Bit length
Data Format Resolution
Allowed values
Actual Output total Current
1
88
uint16_t
16
Q8.8
2
-8
A/bit
Actual Output Voltage
2
72
uint16_t
16
Q8.8
2
-8
A/bit
E-Fuse Current CH1
3
56
uint16_t
16
Q8.8
2
-8
A/bit
E-Fuse Current CH2
4
40
uint16_t
16
Q8.8
2
-8
A/bit
E-Fuse Current CH3
5
24
uint16_t
16
Q8.8
2
-8
A/bit
E-Fuse CH1 state
11
16
bool
1
-
-
true = On
false = Off
E-Fuse CH2 state
12
17
bool
1
-
-
E-Fuse CH3 state
13
18
bool
1
-
-
E-Fuse CH1 overload trip state
15
8
bool
1
-
-
true = tripped
false = Ok
E-Fuse CH2 overload trip state
16
9
bool
1
-
-
E-Fuse CH3 overload trip state
17
10
bool
1
-
-
E-Fuse CH1 short circuit state
19
0
bool
1
-
-
true = tripped
false = Ok
E-Fuse CH2 short circuit state
20
1
bool
1
-
-
E-Fuse CH3 short circuit state
21
2
bool
1
-
-