Puls FIEPOS FPS300.246-036-104 Manual Download Page 2

 

 

 

FPS300.246-036-104 
FPS300.246-049-102 

 

All parameters are specified at 24V, 12.5A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

Apr. 2022 / Rev. 0.1 DS-FPS300-EN 

www.pulspower.com 

2 / 43 

 

I

NDEX

 

 

INDEX .................................................................................. 2

 

 

Intended Use .............................................................. 4

 

 

Installation Instructions ............................................. 4

 

 

AC-Input ..................................................................... 5

 

 

DC-Input ..................................................................... 6

 

 

Input Inrush Current .................................................. 6

 

 

Output ........................................................................ 7

 

 

Hold-up Time ............................................................. 9

 

 

IO-Link Interface ...................................................... 10

 

 

Efficiency and Power Losses .................................... 16

 

 

Lifetime Expectancy ................................................. 17

 

 

MTBF ......................................................................... 17

 

 

Functional Diagram ................................................. 18

 

 

Dimensions and Connector Variants ....................... 19

 

 

User Interface ........................................................... 21

 

 

EMC........................................................................... 24

 

 

Environment ............................................................. 26

 

 

Safety and Protection Features ............................... 27

 

 

Dielectric Strength ................................................... 28

 

 

Approvals and Fulfilled Standards .......................... 29

 

 

Regulatory Compliance ........................................... 29

 

 

Accessories ............................................................... 30

 

21.1.

 

DIN RAIL Mounting KIT: ZM.FPDRA-11 ......... 30

 

21.2.

 

Mounting Braket: ZM.FPMBA-11................... 30

 

21.3.

 

Connectors ...................................................... 31

 

 

Related Products ...................................................... 32

 

 

Application Notes .................................................... 33

 

23.1.

 

Repetitive Pulse Loading ................................ 33

 

23.2.

 

External Input Protection ............................... 33

 

23.3.

 

Inductive and Capacitive Loads ..................... 33

 

23.4.

 

Back Feeding Loads ........................................ 33

 

23.5.

 

Mounting Orientations .................................. 34

 

 

IO-Link Data Types and Description ....................... 35

 

24.1.

 

Cyclic Data ...................................................... 35

 

24.2.

 

Acyclic data ..................................................... 37

 

24.3.

 

Events .............................................................. 43

 

 

 

 

The information given in this document is correct to the best of our knowledge and experience at the time of publication. 
If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the word. As the state 
of  our knowledge and experience is constantly changing, the information in this data sheet is subject to revision. We 
therefore kindly ask you to always use the latest issue of this document (available under www.pulspower.com). 

No part of this document may be reproduced or utilized in any form without our prior permission in writing. 
Packaging and packaging aids can and should always be recycled. The product itself may not be disposed of as domestic 
refuse. 

 

T

ERMINOLOGY AND ABREVIATIONS

 

 

 

PE and   Symbol 

PE is the abbreviation for 

P

rotective 

E

arth and has the same meaning as the symbol 

 

Earth, Ground 

This document uses the term “earth” which is the same as the U.S. term “ground”. 

T.b.d. 

To be defined, value or description will follow later. 

AC 230 V 

A figure displayed with the AC or DC before the value represents a nominal voltage with 
tolerances (usually ±15 %) included. 

E.g.: DC 12 V describes a 12 V battery disregarding whether it is full (13.7 V) or flat (10 V) 

230Vac

 

A figure with the unit (Vac) at the end is a momentary figure without any additional tolerances 
included.

 

50Hz vs. 60Hz

 

As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50Hz mains 
frequency. AC 120V parameters are valid for 60Hz mains frequency.

 

may 

A key word indicating flexibility of choice with no implied preference. 

shall 

A key word indicating a mandatory requirement. 

should 

A key word indicating flexibility of choice with a strongly preferred implementation. 

Us 

Sensor output 

Ua 

Actor output 

 

 

Summary of Contents for FIEPOS FPS300.246-036-104

Page 1: ...and store regenerative energy from breaking motors Various connector options support the different needs of individual applications Please contact PULS for possible options High immunity to transient...

Page 2: ...s the state of our knowledge and experience is constantly changing the information in this data sheet is subject to revision We therefore kindly ask you to always use the latest issue of this document...

Page 3: ...Phase IP54 67 Power Supply Highline Input Voltage 300 300 W Power Class 500 500 W Power Class 241 481 Standard Power Supply with Output Voltage 24 28 V 48 52 V Setting and LED Bar 242 482 Basic Power...

Page 4: ...rviceable parts The tripping of an internal fuse is caused by an internal defect Install the device onto a flat surface with the terminals on the bottom of the device Other mounting orientations requi...

Page 5: ...3 3 Power Power factor typ 0 99 0 99 0 97 At 360 W see Fig 3 4 Start up delay typ 2 s 2 s 2 s At 300 W symmetrical phase voltages see Fig 3 2 Rise time typ 22 ms 22 ms 22 ms At 300 W constant current...

Page 6: ...Fig 4 1 Wiring for DC Input Instructions for DC use a Use a battery or a similar DC source A supply from the intermediate DC bus of a frequency converter is not recommended and can cause a malfunctio...

Page 7: ...highest number will tripped first followed by the next output to ensure that the lower channel number will supply continuous power and see no voltage dips Outputs start sequentially from 1 to 4 with...

Page 8: ...0 Vac 25 C ambient and after a 5 minutes run in time unless otherwise noted Apr 2022 Rev 0 2 FPS300 EN www pulspower com 8 43 Fig 6 1 Sequential start of the outputs Fig 6 2 Tripping of the channel wi...

Page 9: ...the loss of input power The hold up time is output load dependent At no load the hold up time can be up to several seconds The status LED is also on during this time AC 100V AC 120V AC 230V Hold up T...

Page 10: ...er supply provides three categories of data via IO Link They are divided between read only or read and customizable data Control Settings This set of data is customizable The data in control settings...

Page 11: ...ector E Fuse Pre alarm level channel 1 to channel 4 10 100 Defines the threshold for the event Output current pre alarm for each channel Pre Setting 80 PSU total output current Pre alarm level 1 100 A...

Page 12: ...rcuit trip 3 Temperature trip 4 Power budget trip 5 Installation failure trip 6 Sensor fault trip 7 Fatal fault trip Actual trip state of E Fuse channel If the E Fuse has tripped this parameter gives...

Page 13: ...utes 0 1000000 0 59 Total operating hours operating minutes Transient VDE 0160 Counter overall 0 150000 Transient Counter overall Transient VDE 0160 Counter last 2 minutes 0 65535 Transient Counter la...

Page 14: ...m for more than 3s Events Over Load Warning Load higher than allowed Events High Voltage Input Warning Input to high Events Low Voltage Input Warning Input to low Events Power Supply down Warning No l...

Page 15: ...actual output voltage of each output channel internal temperatures tripping status reports etc Process Value range Description Actual Output total Current A Actual Output Voltage V Actual Output Volta...

Page 16: ...application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nominal load for another 25 of the time 75 of the nominal load for another 25 of the time and with...

Page 17: ...34 400h At 24V 6 25A and 25 C MTBF MTBF stands for Mean Time Between Failure which is calculated according to statistical device failures and indicates reliability of a device It is the statistical re...

Page 18: ...fied at 24 V 12 5 A 230 Vac 25 C ambient and after a 5 minutes run in time unless otherwise noted Apr 2022 Rev 0 2 FPS300 EN www pulspower com 18 43 Functional Diagram Fig 12 1 Functional Diagram FPS3...

Page 19: ...lycarbonate Depth 59 mm 2 32 Installation clearances See chapter 2 Weight 1200 g 2 7lb Mating connectors See chapter 21 3 Input connector on power supply X1 M12 S 3pin Male Pin PE connection Pin 1 L P...

Page 20: ...ial Hi grade polycarbonate Depth 59 mm 2 32 Installation clearances See chapter 2 Weight 1200 g 2 7lb Mating connectors See chapter 21 3 7 8 3pin Male Pin PE connection Pin 2 L Pin 3 N IO Link connect...

Page 21: ...The Output Controls consist of an output LED and an Output ON OFF button ON OFF for each output The Output LED displays different running conditions for output in real time The ON OFF is used to switc...

Page 22: ...oint Refer to the current scale on the right sidebar e g 20 LED indicates 24 5 V New point is set After 15 s of non action the PSU will automatically switch to Output Power Mode Set Button Lock To act...

Page 23: ...button PSU with NEC Class II outputs Difference between positive and negative Input Output current of the output are 1 A for 6 6 5 s PSU without NEC Class II outputs Connector negative wire overcurre...

Page 24: ...V Criterion A L to PE N to PE 4kV Criterion A Surge voltage on DC output EN 61000 4 5 to 1kV Criterion A to PE 2kV Criterion A Surge voltage on IO Link EN 61000 4 5 IO Link to PE 1kV Criterion A Condu...

Page 25: ...ics EN 61000 3 2 Class A fulfilled between 0A and 12A load Voltage fluctuations flicker EN 61000 3 3 Pass tested with constant current loads non pulsing This device complies with FCC Part 15 rules Ope...

Page 26: ...ails Over voltage category III According to IEC 60664 1 For TN TT mains systems with earthed neutral and IT star mains systems with insulation monitoring for altitudes up to 2000 m II According to IEC...

Page 27: ...utput shuts down and automatically attempts to restart Class of protection According to IEC 61140 A PE Protective Earth connection is required Ingress protection IP 65 67 According to EN IEC 60529 Ove...

Page 28: ...inforced insulation Type and routine tests are conducted by the manufacturer Field tests may be conducted in the field using the appropriate test equipment which applies the voltage with a slow ramp 2...

Page 29: ...ested for AC 208V L L or L N mains voltages nominal output voltage and nominal output load VDMA 24364 Paint Wetting Impairment Substances Test or LABS Test Tested for Zone 2 and test class C1 accordin...

Page 30: ...S300 EN www pulspower com 30 43 Accessories 21 1 DIN RAIL Mounting KIT ZM FPDRA 11 In addition to screw mounting FIEPOS can easily be attached to a DIN rail using the ZM FPDRA 11 DIN rail mounting kit...

Page 31: ...S female 2 5 6mm 14 17mm Harting HANQ2 0 ZCM hanq20 6104401263900 Q2 0 Set screw male 2 5 6mm 6 12mm Harting HANQ4 0 ZCM hanq40 6104401265100 Q4 0 Set crimp 2 5mm2 IP67 Harting HANQ5 0 ZCF hanq50 6104...

Page 32: ...e DC 24V Nominal Adjustment range 24 28Vdc Factory setting 24 5V Output power Continuous 360W Up to 45 C ambient 300W At 55 C ambient 150W At 70 C ambient Short term up to 5s 600W Below 55 C ambient 3...

Page 33: ...cified continuous output current If the R M S current is higher the unit may respond with a thermal shut down after a period of time 23 2 External Input Protection The device is designed tested and ap...

Page 34: ...this datasheet apply only for the standard mounting orientation The following curves give an indication for allowed output power in different mounting orientations for altitudes up to 2000 m 6560 ft A...

Page 35: ...d PLCs without configuration Process Sub index Bit offset Data type Bit length Data Format Resolution Allowed values Actual Output total Current 1 88 uint16_t 16 Q8 8 2 8 A bit Actual Output Voltage 2...

Page 36: ...Apr 2022 Rev 0 2 FPS300 EN www pulspower com 36 43 Octet 0 1 2 3 4 5 6 7 8 9 Subindex 1 1 2 2 3 3 4 4 5 5 Bit offset 119 112 111 104 103 96 95 88 87 80 79 72 71 64 63 56 55 48 47 40 Octet 10 Subindex...

Page 37: ...2 both default value 3 none button lock Dynamic E Fuse Channel on off 106 0 bool array 8 bit Record 1 R W 0 off 1 on Dynamic Bit 3 7 not used Access via subindex 0 only Chanel 1 0 Chanel 2 1 Chanel 3...

Page 38: ...2 Output current is 5 more than maximum for more than 3s Over Temperature CAP 4 3 bool R bit 3 Temperature Capacitor is higher than 95 C Over Temperature PSU 5 4 bool R bit 4 Temperature of PSU is hig...

Page 39: ...put voltage 79 0 uint16 15 0 Q8 8 2 8 V bit R 0 12544 0 49V Actual average output voltage Actual output current 81 0 uint16 15 0 Q8 8 2 8 V bit R 0 12800 0 50V Actual average output current E Fuse cur...

Page 40: ...pr 2022 Rev 0 2 FPS300 EN www pulspower com 40 43 Parameter Para Index Sub index Data type Bit offset Data Format Resolution Default values Read R Write W Allowed values Description Remaining Enduranc...

Page 41: ...mber of Overcurrents all CHs 88 0 uint16 array 47 0 0 R Number of Overcurrents all Channels E Fuse Number of Overcurrents CH1 1 uint16 47 32 Number of Overcurrents Channel 1 E Fuse Number of Overcurre...

Page 42: ...tatus 36 0 uint8 7 0 R 0 Device is operating properly 1 Maintenance Required 2 Out of Specification 3 Functional Check 4 Failure 0 Device is operating properly 1 Maintenance Required 2 Out of Specific...

Page 43: ...t 0x1804 Warning Input to low Events Power Supply down 0x1805 Warning No link from IO Link Transceiver to Power Supply Events Predictive Maintenance Power Supply 0x1806 Warning The estimated remaining...