Puls CT10.241 Manual Download Page 7

 

 

CT10.241, CT10.241-C1 

 

 

 

 

CT-Series 

3-P

HASE

,

 

24V,

 

10A,

 

240W 

 

 

May 2018 / Rev. 2.0a  DS-CT10.241-EN    All values are typical figures specified at 3x 400Vac, 50Hz input voltage, symmetrical  

phase voltages, 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

7/28 

 

6.

 

DC

 

O

UTPUT

 

The output provides a SELV/PELV rated voltage, which is galvanically isolated from the input voltage. 
The device is designed to supply any kind of loads, including unlimited capacitive and inductive loads. 
The output is electronically protected against overload, no-load and short-circuits. In case of a protection event, 
audible noise may occur. 
 
Output voltage 

Nom. 

24V 

 

Adjustment range 

Min. 

24-28V 

Guaranteed value 

 

Max. 

30V 

This is the maximum output voltage which can occur 
at the clockwise end position of the potentiometer 
due to tolerances. It is not a guaranteed value which 
can be achieved. 

Factory setting output voltage 

Typ. 

24.1V 

±0.2% in “single use” mode at full load, cold unit 

 

Typ. 

24.1V 

±0.2% in “parallel use” mode at 10A, cold unit 

(results to 23.9V ±0.7% at 12A and 25.0V ±0.2% at no 
load) 

Line regulation 

Max. 

10mV 

Between 3x 323 and 3x 576Vac input voltage change 

Load regulation 

Max. 

100mV 

Between 0 and 10A in “single use” mode, static value 

 

Typ. 

1000mV 

Between 0 and 10A in “parallel use” mode, static 
value, see Fig. 6-2 

Ripple and noise voltage 

Max. 

50mVpp 

Bandwidth 20Hz to 20MHz, 50Ohm 

Output current 

Nom. 

12A

1)

 

At 24V and an ambient temperature below 45°C 

 

Nom. 

10A 

At 24V and 60°C ambient temperature 

 

Nom. 

7.5A 

At 24V and 70°C ambient temperature 

 

Nom. 

10.3A

1)

 

At 28V and an ambient temperature below 45°C 

 

Nom. 

8.6A 

At 28V and 60°C ambient temperature 

 

Nom. 

6.5A 

At 28V and 70°C ambient temperature 

 

 

Reduce output current linearly b45°C and +70°C 

Fuse breaking current 

Typ. 

23A 

Up to 20ms once every five seconds, see Fig. 6-1. 
The fuse braking current is an enhanced transient 
current which helps to trip fuses on faulty output 
branches. The output voltage stays above 20V. 

Overload behavior 

 

Continuous current  See Fig. 6-1 

Overload/ short-circuit current 

Max. 

23A 

Continuous current, see Fig. 6-1 

Output capacitance 

Typ. 

6 500µF 

Included inside the power supply 

Back-feeding loads 

Max. 

35V 

The unit is resistant and does not show 
malfunctioning when a load feeds back voltage to 
the power supply. It does not matter whether the 
power supply is on or off. The absorbing energy can 
be calculated according to the built-in large sized 
output capacitor. 

1) This current is also available for temperatures up to +70°C with a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes. 

 

Summary of Contents for CT10.241

Page 1: ...ieved by a synchronous rectification and further technological design details The CT10 241 C1 is equipped with conformal coated pc boards preferred for applications in harsh areas The C Series include...

Page 2: ...orrect to the best of our knowledge and experience at the time of publication If not expressly agreed otherwise this information does not represent a warranty in the legal sense of the word As the sta...

Page 3: ...e factory for inspection The tripping of an internal fuse is caused by an internal defect Install device in an enclosure providing protection against electrical mechanical and fire hazards Install the...

Page 4: ...ircuits up to 32A IEC and 30A UL without additional protection device If an external fuse is utilized do not use circuit breakers smaller than 6A B or C Characteristic to avoid a nuisance tripping of...

Page 5: ...voltage Typ 3x 260Vac Steady state value see Fig 3 1 Shut down voltage Typ 3x 185Vac Steady state value see Fig 3 1 External input protection See recommendations in chapter 2 3AC 400V 3AC 480V Input...

Page 6: ...NRUSH CURRENT An active inrush limitation circuit limits the input inrush current after turn on of the input voltage and after short input voltage interruptions The charging current into EMI suppressi...

Page 7: ...d regulation Max 100mV Between 0 and 10A in single use mode static value Typ 1000mV Between 0 and 10A in parallel use mode static value see Fig 6 2 Ripple and noise voltage Max 50mVpp Bandwidth 20Hz t...

Page 8: ...30A 21 12 3 6 15 24 27 Adjustment Range Output Current Extra current for 20ms Continuous current Factory setting Output Voltage Parallel Use typ 22V 0 4 8 23V 24V 25V 29V 26V 27V 28V 12A 10 6 2 Adjus...

Page 9: ...3 5W 22 8W At 24V 12A 3 phase operation The average efficiency is an assumption for a typical application where the power supply is loaded with 25 of the nominal load for 25 of the time 50 of the nomi...

Page 10: ...gle Parallel 10 FRONT SIDE AND USER ELEMENTS Fig 10 1 Front side A Output Terminals Positive output two identical poles Negative return output two identical poles B Input Terminals L1 L2 L3 Line input...

Page 11: ...m2 Max 4mm2 American Wire Gauge AWG 20 10 AWG 20 10 Max wire diameter including ferrules 2 8mm 2 8mm Recommended tightening torque 1Nm 9lb in 1Nm 9lb in Wire stripping length 7mm 0 28inch 7mm 0 28inch...

Page 12: ...10A and 25 C 2 phase operation 379 000h 410 000h At 24V 5A and 25 C 2 phase operation 102 000h 119 000h At 24V 12A and 25 C 2 phase operation 13 MTBF MTBF stands for Mean Time Between Failure which is...

Page 13: ...1 L2 L3 PE 2kV 4kV Criterion A Criterion A Surge voltage on output EN 61000 4 5 PE 500V 1kV Criterion A Criterion A Conducted disturbance EN 61000 4 6 0 15 80MHz 10V Criterion A Mains voltage dips Dip...

Page 14: ...er voltage category III According to IEC 60664 1 for altitudes up to 2000m II According to IEC 60664 1 for altitudes from 2000 to 6000m and atmospheric pressures from 80 to 47kPa Degree of pollution 2...

Page 15: ...ndant circuit limits the maximum output voltage The output shuts down and automatically attempts to restart Class of protection I According to IEC 61140 A PE Protective Earth connection is required De...

Page 16: ...ed in the field using the appropriate test equipment which applies the voltage with a slow ramp 2s up and 2s down Connect all input terminals together as well as all output poles before conducting the...

Page 17: ...006 Applicable for altitudes up to 2000m Marine GL Germanischer Lloyd classified and ABS American Bureau for Shipping PDA Environmental category C EMC2 Marine and offshore applications SEMI F47 SEMI F...

Page 18: ...S AND WEIGHT Width 62mm 2 44 Height 124mm 4 88 Depth 117mm 4 61 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 750g 1 65lb DIN Rail Use 3...

Page 19: ...ZM1 WALL WALL PANEL MOUNT BRACKET These brackets are used to mount the device on a flat surface or panel without utilizing a DIN rail The two aluminum brackets and the black plastic slider of the uni...

Page 20: ...bracket is used to mount the device sideways with or without utilizing a DIN rail to save installation depth The two aluminum brackets and the black plastic slider of the unit have to be detached so t...

Page 21: ...device is equipped with two input channels each 10A nominal which are individually decoupled by utilizing diode technology The output can be loaded with nominal 20A The device does not require an addi...

Page 22: ...on applies when starting a capacitive load The peak current capability also ensures the safe operation of subsequent circuit breakers of load circuits The load branches are often individually protecte...

Page 23: ...which B and C Characteristic MCBs magnetically trip depending on the wire cross section and wire length The following test results indicate the maximal wire length for a magnetic fast tripping The wi...

Page 24: ...en using multiple devices 22 5 PARALLEL USE TO INCREASE OUTPUT POWER Devices can be paralleled to increase the output power The output voltage of all devices shall be adjusted to the same value 100mV...

Page 25: ...rease when using multiple devices N 1 Redundancy Redundant systems for a higher power demand are usually built in a N 1 method E g four devices each rated for 10A are paralleled to build a 30A redunda...

Page 26: ...uitability of your individual application Using only two legs of a 3 phase system is not included in the agency approval Therefore additional investigations might be necessary during the approval proc...

Page 27: ...ambient temperature for the device In the following test setup the device is placed in the middle of the box no other heat producing items are inside the box The load is placed outside the box The te...

Page 28: ...ting orientation The following curves give an indication for allowed output currents for altitudes up to 2000m 6560ft Fig 22 10 Mounting Orientation A Standard orientation Power Supply OUTPUT INPUT Al...

Reviews: