CT10.241, CT10.241-C1
CT-Series
3-P
HASE
,
24V,
10A,
240W
May 2018 / Rev. 2.0a DS-CT10.241-EN All values are typical figures specified at 3x 400Vac, 50Hz input voltage, symmetrical
phase voltages, 24V, 10A output load, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
28/28
22.9.
M
OUNTING
O
RIENTATIONS
Mounting orientations other than input terminals on the bottom and output on the top require a reduction in
continuous output power or a limitation in the maximum allowed ambient temperature.
The listed lifetime and MTBF values from this datasheet apply only for the standard mounting orientation.
The following curves give an indication for allowed output currents for altitudes up to 2000m (6560ft).
Fig. 22-10
Mounting
Orientation A
(Standard
orientation)
Power
Supply
OUTPUT
INPUT
Allowed Output Current at 24V
0
+45
+70°C
7.5A
10A
12A
Ambient Temperature
+60
Fig. 22-11
Mounting
Orientation B
(Upside down)
Pow
er
Suppl
y
OU
TPUT
INP
UT
Allowed Output Current at 24V
0
+30
+70°C
7.5A
12A
Ambient Temperature
+60
Fig. 22-12
Mounting
Orientation C
(Table-top
mounting)
Allowed Output Current at 24V
0
+25
+70°C
6.5A
12A
Ambient Temperature
+60
Fig. 22-13
Mounting
Orientation D
(Horizontal cw)
Po
w
er
Suppl
y
O
U
TPU
T
INP
UT
Allowed Output Current at 24V
0
+25
+70°C
6.5A
12A
Ambient Temperature
+60
Fig. 22-14
Mounting
Orientation E
(Horizontal ccw)
Po
w
er
Suppl
y
O
U
TPU
T
INP
UT
Allowed Output Current at 24V
0
+25
+70°C
6.5A
12A
Ambient Temperature
+60