EN 

SLA4.100 Installation Manual 

 

 

 

Product Description 

The SLA4.100

 

is a DIN-rail mountable single-phase-input power supply, which provides network 

power for the AS-Interface

®

 system. The AS-Interface

®

 system is a field bus technology, where power 

and data are provided by the same single two-conductor wire. Therefore, special power supplies with 
an integrated data-decoupling circuit are required to prevent the modulated signal voltage on the AS-
Interface

®

 bus from being corrupted. 

 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use to supply 
power to AS-Interface

®

 network systems. 

Do not use this device in equipment where malfunction may cause severe personal injury or threaten 
human life. 
When operating without AS-Interface structure (e.g. in a laboratory test), connect a 470

μ

F/35V 

capacitor between AS-Int and AS-Interface – terminals to avoid output voltage oscillations. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The housing does not provide 
protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of overvoltage category II 
according to IEC 60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT and IT mains networks. The continuous voltage 
between the input terminals and the PE potential must not exceed 300Vac. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 2000m (6560ft). 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 20A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 6A C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 10% and 90% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including inductive and capacitive loads.  
The green DC-OK LED reports a nominal output voltage of a running device. The LED is off as soon 
as the unit is in overload mode. 
Do not parallel devices for higher output currents. 
Do not connect outputs of devices in a series connection for higher output voltages. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 55V. The output 
shuts down and automatically attempts to restart. 
The device is equipped with a manual input range selector. When used on 100-120V mains, set the 
switch into the 115V position. 
The device is equipped with an "IR addressing mode" feature, which is selectable via jumper on the 
front of the unit. The addressing mode interrupts the data communication on the yellow AS-Interface 
cable. Participants with an infrared interface can then quickly be assigned a new ID address by means 
of an infrared programming unit without the need to disconnect them from the AS-Interface cable. 
Afterwards, the "Communication Mode" can be selected again to restart the data communication. The 
red LED reports an active IR-mode and a disabled communication on the yellow AS-Interface cable. 
The device is equipped with a ground fault detection system, which monitors the AS-Interface network. 
Detected ground faults are stored and displayed via the red LED and signaled by a relay contact. 
Pushing the reset button longer than 2s will clear the fault signal. Pushing the reset button shorter than 
2s will initiate a ground fault to test the ground fault. It is essential to connect the shield terminal to PE 
or machine ground. The AS-Interface network must not contain any other ground fault detectors or 
insulation monitoring devices. The ground-fault relay contact (NO-contact) opens with a recognized 
ground-fault. The contact ratings are max. 25Vac or 60Vdc, 0.5A. 

 

Technical Data

 

All values are typical figures specified at 230Vac 50Hz input voltage, 30.6V 
4A output load, 25°C ambient temperature and after a 5 minutes run-in 
time unless otherwise noted. 

Output voltage 

DC 30.6V 

Nominal 

Adjustment range 

Not adjustable 

Factory setting 30.6V 

Output current 

4A 

Below +60°C ambient  

 

3A At 

+70°C 

ambient 

 

Derate linearly b60°C and +70°C 

 

For use on AS-Interface

®

 networks only 

Current limitation 

>4.4A  

Input voltage AC 

AC 100-120V / 
220-240V 

-15% / +10% 
manual select 

Mains frequency 

50 – 60Hz 

±6% 

Input current AC 

2.0 / 1.15A 

At 120 / 230Vac 

Power factor 

0.58 / 0.53 

At 120 / 230Vac 

Input inrush current 

45 / 50A pk 

At 120 / 230Vac, 40°C, 
cold start 

Efficiency 

89.0 / 90.0% 

At 120 / 230Vac 

Power losses 

15.1 / 13.6W 

At 120 / 230Vac 

Hold-up time 

56 / 60ms 

At 120 / 230Vac 

Temperature range 

-10 to +70°C 

 

Max. wire size (litz wire) 

4mm² Power 

terminals 

Wire size AWG 

AWG 20-10 

Power terminals 

Max. wire diameter 

2.8mm Power 

terminals 

Wire stripping length 

7mm / 0.28inch 

Power terminals 

Tightening torque 

1Nm / 9lb.inch 

Power terminals 

Size 

(wxhxd)

 

73x124x102mm Without 

DIN-rail 

Weight 

650g / 1.43lb 

 

 
 

Functional Diagram 

Ground

Fault

Ground Fault

(red)

Input

Fuse

&

Input

Filter

L

N

Output

Overvoltage

Protection

Input

Rectifier

&

Inrush

Limiter

AS-i +

Output

Filter

AS-i-ok

(green)

Power

Converter

Shield

115/230V

Manual

Switch

230

Communication/

IR Mode

AS-i

Decoupling

Unit

IR Mode (red)

AS-i +

AS-i -

AS-i -

Test /

Reset

Ground

Fault

Monitor

 
 

Output Characteristic 

Output voltage

7A

Output current

15V

0V

1A

2A

3A

4A

0A

30.6V

5A

6A

A

B

A: min.

B: typ.

C: max.

C

 

 
 

Temperature Range 

Allowed output current

Ambient temperature

0A

-10

4A

+60

+70°C

3A

A: continuous

B: short term (max. 60s)

A

B

 

 