Check Heating:
  **

Press and hold the up button until the heat symbol appears on the

  LCD.  Within 4 seconds the heat valve should be activated.
 

Note:  

Room temperature must be below the Comfort Heating Limit 

  85.0°F (29.5°C) for heating to become active.

Check Cooling:
  **

Press and hold the down button until the cool symbol appears on

  the LCD.  Within 4 seconds the cool valve should be activated.
 

Note:

  Room temperature must be above the Comfort Cooling Limit 

  65.0°F (18.5°C) for cooling to become active.
  ** To check heating/cooling will depend on the temperature or
  position of the season switch.

TROUBLE SHOOTING TESTS (2-Pipe System)

Voltage:

 When using a voltmeter across "White" and "Black", the  

 

   

voltage must be 120VAC.

To Check Continuity:

  (Using a Voltmeter with all loads connected)

Cooling:

  supply pipe aquastat or season change switch to cool

A) 

When thermostat is calling for Cooling and Low Fan, meter  

 

 

should read 120VAC from "White" to "Orange" and from "White"    

 

to "Yellow".  When Cooling is deactivated, meter should read  

 

 

0VAC from "White" to "Orange" and from "White" to "Yellow".

B)

 When thermostat is calling for Cooling and High Fan, meter  

 

 

should read 120VAC from "White" to "Orange" and from "White"    

 

to "Yellow w/Red Stripe".  When Cooling is deactivated, meter  

 

 

should read 0VAC from "White" to "Orange" and from "White" to    

 

"Yellow w/Red Stripe".

Heating:

  supply pipe aquastat or season change switch to heat

A) 

When thermostat is calling for Heating and Low Fan, meter  

 

 

should read 120VAC from "White" to "Orange" and from "White"    

 

to "Yellow".  When Heating is deactivated, meter should read  

 

 

0VAC from "White" to "Orange" and from "White" to "Yellow".

B)

 When thermostat is calling for Heating and High Fan, meter  

 

 

should read 120VAC from "White" to "Orange" and from "White"    

 

to "Yellow w/Red Stripe".  When Heating is deactivated, meter  

 

 

should read 0VAC from "White" to "Orange" and from "White" to    

 

"Yellow w/Red Stripe".

PSG Controls, Inc.

LIMITED WARRANTY POLICY

PSG Controls, Inc. (Hereinafter referred to as "PSG") warrants the following:
Only cataloged products sold to distributors are warranted to the original purchaser, to 
conform with specifications furnished or approved by PSG, and to be free from defects in 
material and workmanship, for a period of one (1) year from the date of purchase, unless 
specified in writing for a different period.
Any PSG product that proves defective within the above described warranty period will 
be repaired or replaced (at PSG's option) free of any charge if returned to the PSG 
factory at 1225 Tunnel Road, Perkasie, PA. 18944 with transportation charges prepaid.  
Prior to returning this product to PSG, the purchaser shall give PSG notice in writing 
stating how this product fails to fulfill this warranty.  No product shall be accepted for 
repair  or  replacement  without  a  required  written  notice  and  without  prior  written 
authorization and shipping instructions having been received by the purchaser from 
PSG.  Only PSG's factory is authorized to perform services under this warranty.
This warranty does not extend to any product that has been subjected to misuse, abuse, 
neglect, accidents, alterations, improper installation or use in violation of the printed 
instructions  furnished  by  PSG.    This  warranty  neither  applies  to  batteries  nor 
deterioration of, nor damage to the product caused by the use of faulty batteries.  Final 
determination as to whether any product is actually defective rests solely with PSG.  
This warranty is expressly in lieu of all other agreements and warranties, expressed, 
implied, or statutory and PSG has no other obligations or liabilities in connection with this 
product.  In no event shall PSG's obligation or liability hereunder exceed the purchase 
price  of  this  product.    PSG SHALL  NOT IN ANY  EVENT  BE  LIABLE  FOR  ANY 
INCIDENTAL OR CONSEQUENTIAL DAMAGES.  This warranty gives you specific legal 
rights, and you also have other rights which vary from state to state.  Some states do not 
allow  the  exclusion  or  limitation  of  incidental  or  consequential  damages,  or  implied 
warranties, so the above limitations or exclusion may not apply to you.

Toll free technical assistance is available

via our technical hotline: 1-800-523-2558

Mon-Fri, 8:00 A.M. to 4:30 P.M. Eastern Standard Time

1225 Tunnel Road - Perkasie, PA 18944 - 215-257-3621 - Fax 215-257-4288

Web site - www.psgcontrols.com              E-mail - [email protected]