background image

2

 

7. 

From the wire chart found in step 5, assign, according to function, 

 

the cable wire colors to the thermostat wire legend provided below.  

 

Note:  The control feed and the load feed will be connected together 

 

for the 4-pipe installation.  If this is a new installation, record the cable 

 

wire colors in the thermostat legend provided below.

 

Note:

  There is no medium fan in the thermostat.  The wire for the 

 

medium fan needs to be tied off following standard procedures.

New thermostat

wire function

Control Feed

Load Feed

Neutral

Heat
Cool

Low Fan

High Fan

New thermostat

wire color

Black

Orange

White

Red

Blue

Yellow

Yellow w/Red Stripe

Cable

wire color

8. 

Connect the thermostat wires to the cable wires recorded in Step 7.

9. 

Push the wires into the junction box.  Tilt 

  the thermostat so that the bottom of the 
  thermostat is resting on the mounting tabs 
  of the mounting plate.  Push the top of the 
  thermostat towards the wall and secure into 
  place with the self-tapping screw as shown 
  to the right.

Standard
Junction
Box

Screw: 6/32 x 3/4"

Mounting Bracket

Standard
Junction
Box

6. 

Install the mounting bracket to the 

  junction box with the two long 
  mounting screws provided.  
  See mounting detail to the right.
 

Note:  

If application involves a 

  double ganged junction box, 
  a backplate will be required for a 
  complete installation.  
  Please consult your supplier.

9510-0953  Rev -
8-13-13

9. 

Turn power on.

 

 At start up, the fan will automatically run

 

 for three minutes to cycle room air.

BASIC FUNCTIONS

Adjust Temperature Setpoint:

 

Press up button (     ) to raise the temperature (warmer)

 

Press down button (     ) to lower the temperature (cooler)

Select Fan Operation:

 

Press fan button (      ) to select the following fan functions*

 

 

Continuous HIGH speed fan

 

 

Continuous LOW speed fan

 

 

AUTO on/off with automatic speed change

 

 

ECONOMY

 

 

*fan function sequence with auto as the starting point

Change Scale Units:

 

Slide the °F/°C switch to the left to display °F

 

Slide the °F/°C switch to the right to display °C

 

When the °F/°C switch is invoked, the thermostat will reset and  

 

display the default setpoint in the selected scale.

Cycle Timing: 

 (Anti-short cycle protection)

 

3 minute (minimum) dwell time in no-call states 

 

(both heat and cool).  

 

1 minute (minimum) dwell time in call states 

 

(both heat and cool).   

 

Temperature is sampled every 5 seconds.

SYSTEM CHECK:

Check Low Fan Function:

  Press the fan button until the fan indicator on the LCD moves to    
  the LOW  fan position.  
  Low speed fan should turn on immediately.

Check High Fan Function:

  Press the fan button until the fan indicator on the LCD moves to    
  the HIGH fan position.  
  High speed fan should turn on immediately.

Check Heating:
 

Press and hold the up button until the heat symbol appears on    

  the LCD.  Within 4 seconds the heat valve should be activated.
 

Note:  

Room temperature must be below the Comfort Heating  

 

  Limit 85.0°F (29.5°C) for heating to become active.

Check Cooling:
 

Press and hold the down button until the cool symbol appears on   

  the LCD.  Within 4 seconds the cool valve should be activated.
 

Note:

  Room temperature must be above the Comfort Cooling    

  Limit 65.0°F (18.5°C) for cooling to become active.

°F/°C

Room 

Temperature

Indicator

Fan

Icons

Mode

Icons

Cool

Icon

Heat

Icon

Diagnostic

Indicator

Programming
Icons

Scale Indicator

Setpoint
Indicator

ROOM SETPOINT

AUTO
ECON

PROG

ERASE

DIAG

Black

Wiring Diagram 4-pipe Fan Coil

Yellow  LOW

Red

White

Yellow w/red stripe  HIGH

Blue

Cool

Valve

Heat

Valve

Line

Neutral

120VAC

Fan

Orange

Line

Black

Control

Feed

Door Switch, Motion Detector Wiring Diagram 4-pipe Fan Coil

Yellow  LOW

Red

Orange Load Feed

White

Yellow w/red stripe  HIGH

Blue

Cool

Valve

Heat

Valve

Neutral

120VAC

Fan

Motor

Door switch or motion detector control relay
must have a minimum of 10A inductive load 
rating.  In open position fan and valves will be 
deactivated.  In closed position fan and valves 
will be activated.