background image

Installation and Operating Instructions
ES-H2

Specifications:
Set Temperature Range:  

Determined by plug-in setpoint

Plug-in Setpoint Accuracy:  

± 0.5°

Control Accuracy:  

± 1.0°

Sampling Rate:  

Every 30 seconds

System:  

Switch selectable, heat on or off

Economy:  

Switch selectable, on or off

Stages:  

Single stage heating

Differential:  

Switch selectable, 0.5° or 1.0°

Operating Temperature:  

14°F to 105°F

Storage Temperature:  

-4°F to 105°F

Input:  

20VAC to 32VAC

Load Rating:  

1 amp maximum per circuit, 80mA minimum for

 energy 

harvesting

Cycle Rate:  

6 cycles per hour

Common Wire:

  Optional

Delay:  

5 minutes on start-up

Energy Harvesting:  

Switch selectable, on or off

  Enable switch if not connecting a common wire
  Disable switch for sensitive loads, common wire will then be required

Thermostat Charge:

  Thermostat will hold its charge 3.5 hours during

 

a power failure

Enclosure:  

High impact styrene, white

 

Case can be locked, key required

1

Application:

The 

ACCUSTAT®

                         model ES-H2 thermostat was designed

to operate 24VAC to 30VAC heating systems.  The control can be easily
placed in economy mode by simply sliding a switch. This thermostat is
MERCURY FREE!!  The 

ACCUSTAT®                           

models utilize

pre-set plug-in temperature setpoints to activate the circuits.  Room air
temperature is measured by a microprocessor and compared with the
plug-in setpoint temperature.  The thermostat has a locking cover to
prevent tampering.

Operating Conditions:

The electronic mechanisms incorporated within this unit REQUIRE
operating conditions similar to other electronic devices intended for
INDOOR USE ONLY, such as would be acceptable for TV and similar
household appliances.  Relative humidity must be less than 95% and
the atmosphere must be non-condensing.  Air quality must be main-
tained, FREE of heavy dust or debris which may infiltrate the interior
of this device.  Installation in any space which is unfinished or under-
going repainting or general rehabilitation is also considered product
abuse.  This device should be removed from service during any local
construction activity.

Cleaning:

This device incorporates a high impact styrene enclosure which is
easily cleaned with a dry cloth or vacuum brush.  Occasional soiling
may be cleaned with a soft cloth lightly dampened with water and/or
mild cleaning solution.  IN NO CASE should this device be directly
sprayed with or exposed to free flowing liquids, including water, which
could penetrate its interior.

FAILURE TO OBSERVE ANY OF THE ABOVE CONDITIONS OF USE
WILL COMPLETELY VOID THE SUPPLIER WARRANTY.

 

                             

 

                                  CAUTION

MAKE SURE UNIT IS PROPERLY CONNECTED.  DAMAGE TO THE
CONTROL CAN BE CAUSED BY MISWIRING, WHICH WILL VOID
THE WARRANTY.

TO OPEN:
1.

  Align key with slot and insert all the way

2.

  Locking pin will emerge.  Pull out completely

3.

  Gently squeeze left side of cover to

 release 

catches

4.

  Let right side work as a hinge

 

Swing cover out and remove

 

TO CLOSE: 

(Reverse Procedure)

1.

  Hinge right side of cover and close it

2.

  Gently squeeze left side of cover and

 snap 

shut

3.

  Orient the locking pin as shown and

 

slide in until end is below surface of

 

cover (audible snap is heard when

 

pin is properly seated) 

 

1
Insert

3

4

Squeeze

2

Remove

Lift and
Rotate

Environmentally Friendly
MERCURY FREE!!

Use 

ONLY

 

ACCUSTAT®

Temperature Setpoints

ECONOMY

OFF  ON

HEAT
OFF  ON

ATTENTION: This product does not contain mercury.
This product may be replacing a product containing
mercury.
Do not place the old product in the household trash. 
For more information on recycling and proper disposal
visit TRC’s website www.thermostat-recycle.org
Should a tube break, do not touch any spilled mercury.
Wear non-absorbent gloves, collect any spilled mercury
and place it in a sealed container. Contact your local waste
management authority for recycling and proper disposal
instructions.