background image

9510-0846  Rev A
11-16-09

PSG Controls, Inc.

LIMITED WARRANTY POLICY

PSG Controls, Inc. (Hereinafter referred to as "PSG") warrants the following:
Only cataloged products sold to distributors are warranted to the original purchaser, to 
conform with specifications furnished or approved by PSG, and to be free from defects in 
material and workmanship, for a period of one (1) year from the date of purchase, unless 
specified in writing for a different period.
Any PSG product that proves defective within the above described warranty period will 
be repaired or replaced (at PSG's option) free of any charge if returned to the PSG 
factory at 1225 Tunnel Road, Perkasie, PA. 18944 with transportation charges prepaid.  
Prior to returning this product to PSG, the purchaser shall give PSG notice in writing 
stating how this product fails to fulfill this warranty.  No product shall be accepted for 
repair or replacement without a required written notice and without prior written 
authorization and shipping instructions having been received by the purchaser from 
PSG.  Only PSG's factory is authorized to perform services under this warranty.
This warranty does not extend to any product that has been subjected to misuse, abuse, 
neglect, accidents, alterations, improper installation or use in violation of the printed 
instructions furnished by PSG.  This warranty neither applies to batteries nor 
deterioration of, nor damage to the product caused by the use of faulty batteries.  Final 
determination as to whether any product is actually defective rests solely with PSG.  
This warranty is expressly in lieu of all other agreements and warranties, expressed, 
implied, or statutory and PSG has no other obligations or liabilities in connection with this 
product.  In no event shall PSG's obligation or liability hereunder exceed the purchase 
price of this product.  PSG SHALL NOT IN ANY EVENT BE LIABLE FOR ANY 
INCIDENTAL OR CONSEQUENTIAL DAMAGES.  This warranty gives you specific legal 
rights, and you also have other rights which vary from state to state.  Some states do not 
allow the exclusion or limitation of incidental or consequential damages, or implied 
warranties, so the above limitations or exclusion may not apply to you.

Toll free technical assistance is available

via our technical hotline: 1-800-523-2558

Mon-Fri, 8:00 A.M. to 4:30 P.M. Eastern Standard Time

1225 Tunnel Road - Perkasie, PA 18944 - 215-257-3621 - Fax 215-257-4288

Web site - www.psgcontrols.com              E-mail - [email protected]

R

PSG Controls, Inc.

2

GENERAL INSTRUCTIONS:

This control should be installed and serviced by a qualified contractor.
 

1.       Caution:  

Make sure that power to the control has been turned 

 

off before doing any installing or service work.  Class 2 transformers

 

can be damaged if a short circuit occurs when disconnecting wires

 

from the old thermostat.

2.

  All wiring must conform to local and state codes and ordinances.

3.

  A thorough check-out of the system must be made after the 

 

control has been installed.

4. 

This thermostat was designed to operate as a energy harvesting

 

control.  A common wire is optional.  If the thermostat is connected

 

directly to a logic board at the equipment, in order for it to function,

 

it may be necessary to connect a common to the thermostat and

 

turn off the energy harvesting switch.

MOUNTING THE CONTROL:
1.

  Open case as shown.

2.

  Choose a location about 5 feet above the floor, in an area where

 

there is good air circulation.  Such an area will provide an average

 room 

temperature.

3. 

Do NOT mount thermostat where it may be affected by drafts, hot

 

or cold air from ducts or radiant heat from the sun or appliances.

4. 

Pull thermostat cable through hole in wall or outlet box.

5. 

Plug wall hole to prevent drafts which may affect thermostat.

6.

  Use the screws supplied to mount the case on the wall.

7.

  This control is not position sensitive.  However, heat rises and

 

some heating does occur in the control.  It is recommended that

 

the unit be mounted with the top up.

INSTALLING PLUG-IN SETPOINTS:

Installing the pre-set plug-in temperature setpoints is as easy as
installing a fuse.  Direction does not matter.  The large plated tabs
must be pointed toward the thermostat.  Press the plug-in setpoint
firmly into position.

NOTE:  The plug-in setpoints must be installed at all times.

 

Removal of the setpoints will disable the thermostat.

SW5
Configuration
Switches

Wire
Terminal
Block

Energy
Harvesting
Switch

H1 = Comfort heat setpoint
H2 = Economy heat setpoint

X

RH

W1

SW5 Settings:

1234

OFF

ON

Position 1, Not used

Position 2, Not used

Position 3, Not used

Position 4, differential, OFF (0.5°), ON (1.0°)