38
Picture 54: Error mode
– Outputs
Picture 55: Error mode - Outputs -
Last state
Picture 56: Error mode
– Outputs - n.o.
active / n.c. idle (inactive) / Analog output
3 mA
Error mode
This setting determines the outputs behavior in case of LM_ 100 failure.
Last condition
LM_ 100 outputs will take on the last condition before
failure.
n.o. active / n.c. idle (inactive) / analog output 3 mA
In case of failure, LM_ 100 outputs will take on the
following condition:
n.o. active (closes)
n.c. idle
–inactive- (remains closed)
Analog output will deliver 3 mA.
n.o. idle (inactive) / n.c. active / analog output 21 mA
In case of failure, LM_ 100 outputs will take on the
following condition:
n.o. idle
–inactive- (remains open)
n.c. active (opens)
Analog output will deliver 21 mA.
Picture 57: Error mode -Outputs - n.o. idle
(inactive)/ n.c. active / Analog output 21
mA