Type and deadband
–
Detector m
:
Object
Type / Deadband
Description
Lx Current
Normalized [0-100 %]
Normalized primary current according to reference value on
tab I/O Settings.
Example: Reference value = 300/1
Value 0
0 A
Value 1.0
300 A
Normalized [0-120 %]
Normalized primary current according to reference value on
tab I/O Settings times 1.2.
Example: Reference value = 300/1
Value 0
0 A
Value 1.0
360 A
Float [SI]
Primary current in Amperes, as floating point.
Scaled [SI*1]
Primary current in Amperes, as integer.
Scaled [SI*10]
Primary current in 0.1 Amperes, as integer.
Scaled [SI*100]
Primary current in 0.01 Amperes, as integer.
Lx Current
Deadband [%]
Set as a percentage of to reference value on tab I/O Settings.
Example: Reference value = 300/1
1 %
3 A
LN Current
Type
Identical to
”Lx Current”
Deadband
Identical to
”Lx Current”
Max Fault Current
Float [SI]
Primary current in Amperes, as floating point.
Scaled [SI*1]
Primary current in Amperes, as integer.
Deadband [%]
Not used. Sent upon detected overcurrent (OC).
Max Current
Type
Identical to ”Lx Current” ovan.
Deadband
Identical to ”Lx Current” ovan.
Avg Current Period
Type
Identical to ”Lx Current” ovan.
Deadband
Identical to ”Lx Current” ovan.
Fault Phase
Float [SI]
Faulty phase, as floating point.
Scaled [SI*1]
Faulty phase, as integer.
Deadband
Not used. Sent upon detected fault (OC/EF).