7.2.2.1 IEC 60870-5-101/104
– Common
Settings
–
Common
:
Parameter
Description
Range
Factory value
Unit
Common address
(CA)
Common ASDU address.
Can have range 1 octet or 2 octets.
1..254
1..65 534
1
-
Use end of init
(M_EI)
The device shall send a startup message.
Yes or No
Yes
-
Slave interface
Choice of remote control interface
No slave,
-101 slave,
-104 slave
-104 slave
-
Select timeout
Specifies how long to wait for the Execute
command after an object has been Selected. If no
Execute command arrives within the set time, the
order will be interrupted.
1..3 600
30
s
Cyclic analog
transmission
Period for cyclic transmission of analog values.
0..86 400
0
s
IEC -101/-104 master
1
Option
Master interface
Choice of interface to sub-slaves
No master,
-101 master
No master
-
1
IEC -101 master is an option that needs to be specified upon order. This option is not available if the device is
configured for IEC -101 slave and connected to PDCIO.