Settings -
101 master
1
:
Parameter
Description
Range
Factory value
Unit
Protocol settings:
Use master common address
See description on previous page.
Yes or No
Yes
-
Time tag type
Specifies the type of time format
IPC402x uses.
-
2
CP56
-
Link address
(LA) size
Size of link address.
0..2
1
oktett
Common address
(CA) size
Size of RTU address.
1..2
2
oktett
Object address
(OA) size
Size of Object address.
1..3
3
oktett
Cause of transmission
(COT) size
Size of
”COT”.
1..2
2
oktett
Slave link addresses, Slave x:
Link address x
Link address of local slave(s).
Can have length 1 or two octets.
0 means no slave is connected.
0..254
0..65 534
0
3
-
Common address x
RTU address for local slave(s).
Can have length 1 or 3 octets.
0 means no slave is connected.
0..254
0..65 534
0
-
Port settings:
4
Port type
2-wire RS-485
-
1
-
-
Baudrate
Communication speed.
1 200, 2 400,
4 800, 9 600
9 600
Bit/s
1
IEC -101 master is an option that must be specified upon order.
2
This is for information only and cannot be changed by the user.
3
Address 0 means that no slave is expected to be connected.
4
The port is set to 8-E-1, i.e., 8 data bits, even parity and 1 stop bit.