Harsco Industrial Patterson-Kelley ProtoNode Startup Guide
Page 8 of 38
ProtoCessor
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.protocessor.com
Tel
: (408) 964 4444
Fax
: (408) 964 4425
Toll Free
: (800) 317 8319
2.3.3.1
S0 – S3 DIP Switch Configuration Settings
A.
BACnet MS/TP and BACnet IP for ENVI boilers
The following chart describes S0 - S3 DIP Switch configuration settings for the ENVI’s 1 through 16 boilers
applications to support
BACnet MS/TP and BACnet/IP
on a ProtoNode RER (Part # FPC-N34-103-126-
0710).
ProtoNode RER FPC-N34-103-126-0710
ProtoNode S Bank DIP Switches
Profile
S0
S1
S2
S3
BACnet IP/BACnet MS/TP 1 ENVI
Off
Off
Off
Off
BACnet IP/BACnet MS/TP 2 ENVI
On
Off
Off
Off
BACnet IP/BACnet MS/TP 3 ENVI
Off
On
Off
Off
BACnet IP/BACnet MS/TP 4 ENVI
On
On
Off
Off
BACnet IP/BACnet MS/TP 5 ENVI
Off
Off
On
Off
BACnet IP/BACnet MS/TP 6 ENVI
On
Off
On
Off
BACnet IP/BACnet MS/TP 7 ENVI
Off
On
On
Off
BACnet IP/BACnet MS/TP 8 ENVI
On
On
On
Off
BACnet IP/BACnet MS/TP 9 ENVI
Off
Off
Off
On
BACnet IP/BACnet MS/TP 10 ENVI
On
Off
Off
On
BACnet IP/BACnet MS/TP 11 ENVI
Off
On
Off
On
BACnet IP/BACnet MS/TP 12 ENVI
On
On
Off
On
BACnet IP/BACnet MS/TP 13 ENVI
Off
Off
On
On
BACnet IP/BACnet MS/TP 14 ENVI
On
Off
On
On
BACnet IP/BACnet MS/TP 15 ENVI
Off
On
On
On
BACnet IP/BACnet MS/TP 16 ENVI
On
On
On
On
Support for 1 through 16 ENVI’s to Metasys N2 or Modbus TCP see Appendix B.2
Support for 1 Love Controller to support BACnet MS/TP, BACnet/IP, Metasys N2 or Modbus TCP
see Appendix B.2
S Bank DIP Switches