Harsco Industrial Patterson-Kelley ProtoNode Startup Guide
Page 7 of 38
ProtoCessor
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.protocessor.com
Tel
: (408) 964 4444
Fax
: (408) 964 4425
Toll Free
: (800) 317 8319
DIP switches A0 – A7 can also be used to set the MAC Address for BACnet MS/TP and BACnet/IP
Figure 1: A0 – A7 DIP Switches
Please refer to Appendix B.3 for the full range of addresses to set Node-ID/Device Instance.
NOTE:
When setting DIP Switches, please ensure that power to the board is OFF.
2.3.2
Setting the Serial Baud Rate (DIP Sw itch B0 – B3) for BACnet MS/TP and Metasys
N2 ProtoNodes
DIP Switches B0 – B3 can be used to set the serial baud rate to match the baud rate provided by the
Building Management System for BACnet MS/TP.
Metasys N2 is always defaulted to 9600 baud and the B bank is disabled.
B0 B1 B2 B3
Figure 2: B0 – B3 DIP Switches
2.3.2.1
Baud Rate DIP Switch Selection
Baud
B0
B1
B2
B3
9600
On On On Off
19200 Off Off Off On
38400 On On Off On
57600 Off Off On On
76800 On Off On On
2.3.3
Using S0 – S3 bank of DIP Switches to select and load Configuration Files for ENVI
and Love Controller
The S bank of DIP switches, S0 - S3 is used to select and load a configuration file from a group of
pretested/preloaded configuration files which are stored in the ProtoNode RER FPC-N34-103-126-0710
(BACnet MS/TP, BACnet/IP, Modbus TCP, Metasys N2) and the ProtoNode LER FPC-N35-103-401-0771
(LonWorks).
S0 S1 S2 S3
Figure 3: S0 – S3 DIP Switches