Appendix B.

 

Vendor Information 

Appendix B.1.

 

ENVI and Love Controller Modbus RTU COM Settings 

 

Settings 

ENVI  Boiler 1  ENVI  Boiler 2  ENVI  Boiler 3  Love Controller 

Baud Rate 

9600 

9600 

9600 

9600 

Data Bits 

None 

None 

None 

None 

Stop Bits 

Parity 

Modbus Node ID 

Appendix B.2.

 

ENVI Modbus RTU Mappings to BACnet MS/TP, BACnet IP, Metasys and LonWorks 

Map_Descriptor_Name 

BACnet 

Object Type 

BACnet 

Object Id 

N2 Data 

Type 

N2 Point 
Address 

Lonworks Name 

Lonworks SNVT 

Type 

State 

AI 

AI 

nvoXXState 

SNVT_count_inc_f 

Supply Temp 

AI 

AI 

nvoXXSupplyTmp 

SNVT_count_inc_f 

Return Temp 

AI 

AI 

nvoXXReturnTmp 

SNVT_count_inc_f 

DHW Temp 

AI 

AI 

nvoXXDHWTmp 

SNVT_count_inc_f 

Header Temp 

AI 

AI 

nvoXXHeaderTmp 

SNVT_count_inc_f 

Firing Rate 

AI 

AI 

nvoXXFiringRate 

SNVT_lev_percent 

Flue Gas Temp 

AI 

AI 

nvoXXFlueGasTmp 

SNVT_count_inc_f 

HX Temp 

AI 

AI 

nvoXXHXTmp 

SNVT_count_inc_f 

Outside Temp 

AI 

AI 

nvoXXOutsideTmp 

SNVT_count_inc_f 

Flame Signal 

AI 

10 

AI 

10 

nvoXXFlameSignal 

SNVT_count_inc_f 

CH Setpoint 

AV 

11 

AO 

11 

nvi/nvoXXCHSP 

SNVT_count_inc_f 

DHW Setpoint 

AV 

12 

AO 

12 

nvi/nvoXXDHWSP 

SNVT_count_inc_f 

Boiler Operation 

AV 

13 

AO 

13 

nvi/nvoXXBlrOperatn 

SNVT_count_inc_f 

High Outdoor Air Temp 

AV 

14 

AO 

14 

nvi/nvoXXHiOATmp 

SNVT_count_inc_f 

Min Outdoor Air Setpoint 

AV 

15 

AO 

15 

nvi/nvoXXMinOASP 

SNVT_count_inc_f 

Low Outdoor Air Temp 

AV 

16 

AO 

16 

nvi/nvoXXLoOATmp 

SNVT_count_inc_f 

Max Outdoor Air Setpoint 

AV 

17 

AO 

17 

nvi/nvoXXMaxOASP 

SNVT_count_inc_f 

Outdoor Air Shutdown Temp 

AV 

18 

AO 

18 

nvi/nvoXXOAShtdwnTmp  SNVT_count_inc_f 

Night Setback 

AV 

19 

AO 

19 

nvi/nvoXXNightStback 

SNVT_count_inc_f 

Error Code 

AI 

20 

AI 

20 

nvoXXErrorCode 

SNVT_count_inc_f 

Analog In 

AI 

21 

AI 

21 

nvoXXAnalogIn 

SNVT_volt 

Analog Out 

AI 

22 

AI 

22 

nvoXXAnalogOut 

SNVT_volt 

Ignitions 

AI 

23 

AI 

23 

nvoXXIgnitions 

SNVT_count_inc_f 

Burner High Hours 

AI 

24 

AI 

24 

nvoXXBrnrHiHrs 

SNVT_time_hour 

Burner Medium Hours 

AI 

25 

AI 

25 

nvoXXBrnrMedHrs 

SNVT_time_hour 

Burner Low Hours 

AI 

26 

AI 

26 

nvoXXBrnrLoHrs 

SNVT_time_hour 

Water Level 

BI 

27 

DI 

27 

nvoXXWaterLvl 

SNVT_switch 

Low Gas Pressure 

BI 

28 

DI 

28 

nvoXXLoGasPrs 

SNVT_switch 

Air Pressure 

BI 

29 

DI 

29 

nvoXXAirPrs 

SNVT_switch 

Blocked Flue 

BI 

30 

DI 

30 

nvoXXBlckdFlue 

SNVT_switch 

Summary of Contents for ProtoNode LER

Page 1: ...ustrial Patterson Kelley ENVI Control Systems and Love Controller To Building Automation Systems BACnet MS TP BACnet IP Metasys N2 Modbus TCP and LonWorks APPLICABILITY EFFECTIVITY Explains the ProtoN...

Page 2: ...toNode Startup Guide Page 2 of 38 ProtoCessor 1991 Tarob Court Milpitas California 95035 USA Web www protocessor com Tel 408 964 4444 Fax 408 964 4425 Toll Free 800 317 8319 email support protocessor...

Page 3: ...d Protocol 14 3 4 Wiring the ProtoNode LER Field Port to a LonWorks network 15 3 5 Power Up the ProtoNode RER or LER 15 4 Commissioning the ProtoNode LER on a LonWorks network 16 4 1 Commissioning the...

Page 4: ...5 bottom 10 Figure 5 Pin outs for the ENVI s Modbus RS 485 port and power to the ProtoNode 11 Figure 6 Pin outs for the Love s Modbus RS 485 port and power to the ProtoNode 11 Figure 7 Wiring diagram...

Page 5: ...AE 2 Metasys is a registered trademark of Johnson Controls Inc 3 4 LonWorks is a registered trademark of Echelon Corporation The BTL Mark on the ProtoNode RER is a symbol that indicates to everyone th...

Page 6: ...85 interface located on the ProtoNode s 6 pin connector See Section 3 6 Power up the ProtoNode RER and LER See Section 3 6 7 Commission the ProtoNode on the LonWorks Network This needs to be done by t...

Page 7: ...s B0 B3 can be used to set the serial baud rate to match the baud rate provided by the Building Management System for BACnet MS TP Metasys N2 is always defaulted to 9600 baud and the B bank is disable...

Page 8: ...BACnet IP BACnet MS TP 2 ENVI On Off Off Off BACnet IP BACnet MS TP 3 ENVI Off On Off Off BACnet IP BACnet MS TP 4 ENVI On On Off Off BACnet IP BACnet MS TP 5 ENVI Off Off On Off BACnet IP BACnet MS...

Page 9: ...es Profile S0 S1 S2 S3 LonWorks 1 ENVI Off Off Off Off LonWorks 2 ENVI On Off Off Off LonWorks 3 ENVI Off On Off Off LonWorks 4 ENVI On On Off Off LonWorks 5 ENVI Off Off On Off LonWorks 6 ENVI On Off...

Page 10: ...ornia 95035 USA Web www protocessor com Tel 408 964 4444 Fax 408 964 4425 Toll Free 800 317 8319 email support protocessor com 3 INTERFACING THE PROTONODE TO ENVI AND LOVE CONTROLLER 3 1 ProtoNode RER...

Page 11: ...4 4425 Toll Free 800 317 8319 email support protocessor com 3 2 Wiring Connections to ProtoNode RER and LER for the ENVI and Love Controller ProtoNode 6 Pin Phoenix connector Pin outs to ENVI s and Lo...

Page 12: ...o not connect Ground between ENVI and the ProtoNode s RS485 Ground Figure 7 Wiring diagram for the EVNI s Modbus RTU RS 485 to the ProtoNode s RS 485 port 3 2 2 Biasing the Modbus RS 485 Network An RS...

Page 13: ...the RS 485 trunk must be properly terminated at each end If the ProtoNode is placed at one of the ends of the trunk you turn the Blue RS 485 End of Line Terminating switch to ON position On short cab...

Page 14: ...2 networks Connect BACnet MS TP or N2 RS485 to the 3 pin RS485 connector on ProtoNode RER as shown below Figure 10 Connection from ProtoNode to RS 485 BMS Field Protocol BACnet MS TP or Metasys N2 See...

Page 15: ...otoNode to the field network with the LonWorks terminal using a twisted pair non shielded cable LonWorks has no polarity Figure 12 ProtoNode LER LonWorks FFT 10 2 wire screw terminal 3 5 Power Up the...

Page 16: ...enclosure to access the Service Pin See the illustration on the ProtoNode LER as to which way to toggle the screw driver during commissioning If an XIF file is required see steps Section 4 4 1 to gene...

Page 17: ...4444 Fax 408 964 4425 Toll Free 800 317 8319 email support protocessor com For Windows XP and Windows 7 select Use the following IP address Click twice Open a web browser and go to the following addr...

Page 18: ...Connect the PC to the ProtoNode via the Ethernet port Figure 15 Ethernet port location of ProtoNode Connect a standard CAT5 Ethernet cable straight through or cross between the PC and ProtoNode The D...

Page 19: ...s TCP via GUI Open a PC web browser enter the default IP address of the ProtoNode 192 168 1 24 and connect to the ProtoNode From the GUI main home page click on setup and then Network Settings to ente...

Page 20: ...tartup Guide Page 20 of 38 ProtoCessor 1991 Tarob Court Milpitas California 95035 USA Web www protocessor com Tel 408 964 4444 Fax 408 964 4425 Toll Free 800 317 8319 email support protocessor com Fig...

Page 21: ...ve the BMS Integrator on site A Serial or USB to RS 485 converter is needed to test BACnet MS TP 6 1 Downloading Chipkin Automation s CAS Explorer and Requesting an Activation Key To request a 2 week...

Page 22: ...P and BACnet Ethernet boxes o Set the BACnet MSTP MAC address to 0 o Set the BACnet MSTP Baud Rate to 38400 o Click Ok o On the bottom right hand corner make sure that the BACnet MSTP box is green o C...

Page 23: ...correct baud rate and device instance o Verify IP address setting o Verify wiring If the problem still exists a log needs to be taken and sent to FieldServer See Appendix A 2 Appendix A 2 Take Log Wi...

Page 24: ...Go to Right click on Local Area Connection Properties Highlight For Windows XP and Windows 7 select Use the following IP address Click twice Double click on the FST Diag Utility Step 1 Select a Field...

Page 25: ...n to these DOS prompts This step may take a few minutes depending on the chosen Log Type and computer speed When the Utility is finished you will be presented with a log of events that have occurred S...

Page 26: ...R and LER RTC Unused RUN The RUN LED will start flashing 20 seconds after power indicating normal operation ERR The SYS ERR LED will go on solid 15 seconds after power up It will turn off after 5 seco...

Page 27: ...SNVT_count_inc_f Outside Temp AI 9 AI 9 nvoXXOutsideTmp SNVT_count_inc_f Flame Signal AI 10 AI 10 nvoXXFlameSignal SNVT_count_inc_f CH Setpoint AV 11 AO 11 nvi nvoXXCHSP SNVT_count_inc_f DHW Setpoint...

Page 28: ...on BI 43 DI 43 nvoXXFrstPrtctn SNVT_switch DHW Mode BI 44 DI 44 nvoXXDHWMode SNVT_switch CH Mode BI 45 DI 45 nvoXXCHMode SNVT_switch ET Month AI 46 AI 46 nvoXXETMonth SNVT_count_inc_f ET Day AI 47 AI...

Page 29: ...nk of DIP switches below ProtoCessor A3 A8 DIP switches are disabled ProtoNode RER ProtoCarrier DIP Switches ProtoCessor DIP Switches Remove Cover Profile FPC N34 103 126 0710 S0 S1 S2 S3 A1 A2 A3 A4...

Page 30: ...bus RTU 5 ENVI Off Off On Off Off On Off Off Off Off Off Off Modbus TCP Modbus RTU 6 ENVI On Off On Off Off On Off Off Off Off Off Off Modbus TCP Modbus RTU 7 ENVI Off On On Off Off On Off Off Off Off...

Page 31: ...Off On On Off On 13 Off Off Off Off On On On Off 14 Off Off Off Off On On On On 15 Off Off Off On Off Off Off Off 16 Off Off Off On Off Off Off On 17 Off Off Off On Off Off On Off 18 Off Off Off On Of...

Page 32: ...Off Off On On On Off On Off 58 Off Off On On On Off On On 59 Off Off On On On On Off Off 60 Off Off On On On On Off On 61 Off Off On On On On On Off 62 Off Off On On On On On On 63 Off On Off Off Off...

Page 33: ...f On On Off Off On On On 103 Off On On Off On Off Off Off 104 Off On On Off On Off Off On 105 Off On On Off On Off On Off 106 Off On On Off On Off On On 107 Off On On Off On On Off Off 108 Off On On O...

Page 34: ...147 On Off Off On Off On Off Off 148 On Off Off On Off On Off On 149 On Off Off On Off On On Off 150 On Off Off On Off On On On 151 On Off Off On On Off Off Off 152 On Off Off On On Off Off On 153 On...

Page 35: ...On Off Off Off Off Off On 193 On On Off Off Off Off On Off 194 On On Off Off Off Off On On 195 On On Off Off Off On Off Off 196 On On Off Off Off On Off On 197 On On Off Off Off On On Off 198 On On O...

Page 36: ...ff On On On 231 On On On Off On Off Off Off 232 On On On Off On Off Off On 233 On On On Off On Off On Off 234 On On On Off On Off On On 235 On On On Off On On Off Off 236 On On On Off On On Off On 237...

Page 37: ...5 cm L x 8 3 cm W x 4 1 cm H 4 5 x 3 2 x 1 6 in Weight 0 2 kg 0 4 lbs Operating Temperature 40 C to 75 C 40 F to167 F Surge Suppression EN61000 4 2 ESD EN61000 4 3 EMC EN61000 4 4 EFT Humidity 5 90 R...

Page 38: ...s approval or which have been subjected to accident improper maintenance installation or application or on which original identification marks have been removed or altered This Limited Warranty also w...