T e c h n i c a l N o t e b o o k . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
T e c h n i c a l T r a i n i n g
Code Parameter
Units Description
Factory
setting
Possible to
change?
d.70
Forcing of 3-way valve (SB version
only)
-
0 = normal mode
1 = do not use (blocking of the 3-way valve in the centre
position)
2 = heating mode only
0
yes
d.71
Max. Heating flow temperature setting.
°C
Select a value between 45 and 80°C. (factory setting 75°C)
75
yes
Note: The heating setting is adjustable via the user interface from 10 to 73°C. Factory setting = 60°C.
d.77
Domestic hot water power (SB version
only)
kW
This item allows limiting of the domestic hot water power
(factory setting = max. setting).
P. max. of
the model
yes
d.80 Heating operating time
100h
Blocks
Burner on operating time (100h block)
1 = 100 hours
(not possible to reset)
0
read only
d.81
Hot water operating time
100h
Blocks
Burner on operating time (100h block)
1 = 100 hours
(not possible to reset)
0
read only
d.82 Number of burner ignitions in heating
100
ign.
blocks
1 = 100 ignitions
(not possible to reset)
0
read only
d.83
Number of burner ignitions in hot water
100
ign.
blocks
1 = 100 ignitions
(not possible to reset)
0
read only
d.85
Minimum power of the appliance
kW
This parameter is used to increase the minimum output in
the case that the boiler is installed with C43p (specific to Be,
FR and NL). Keep the factory setting in all other cases.
d.90 Detection of an e-bus room thermostat
-
0 = not detected
1 = detected
-
read only
d.93 Product code setting
-
Product code
2
yes
Details for d93 parameter
Model
type
nat. gas G20 LPG G30/31
Gepard
23 MOV
0
4
23 MTV
1
1
Panther
12 KOO
0
7
12 KTO
1
1
25 KOO
2
8
25 KOV
3
8
25 KTO
4
4
25 KTV
5
5
30 KTV
6
6
d.94 Reinitialise fault list
-
This function is used to clear the fault list on the appliance.
0 = no
1= reset fault list
0
yes
d.95 Program versions
°C
Gives the version of: 1. Main circuit board
2. Display card (Interface)
-
read only
d.96 Return to factory settings
-
This function returns the parameters to the factory settings
1
yes
The values with a green background are only accessible from the After-Sales menu (access code = 35)