Regulation:
• Warmstart function:
Warmstart function is to maintain temperature in the primary circuit of the boiler to improve the domestic hot water comfort:
- Reduction of waiting times in hot tap water
- Water conservation
This function only affects Panther KOV and KTV.
Principle of operation :
The function is activated when the primary descends to 30K below the hot water setting: the burner lights and switches off at the hot
water setting minus 10K.
Warmstart function is enabled or disabled by the installer menu (d66)
ECO picto is displayed when the DHW set-point is under 50°C.