104S
♦
ProLinx Gateway
IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 77 of 157
January 22, 2010
C_SE_NA and C_SE_NB
The measured normalized point command uses one word with word-addressing. For
example, if you configured the following points:
The following table describes how these points would be used.
Inf. Object Address
104S gateway Database Address
1100
Word 2000 (Word address 2000)
400
Word 10 (Word address 10. Must match the
configuration of point 400 in M_ME_NA.)
1101
Word 2001 (Word address 2001)
401
Word 12 (Word address 12. Must match the
configuration of point 401 in M_ME_NA.)
1102
Word 2001 (Word address 2001)
402
Word 18 (Word address 18. Must match the
configuration of point 402 in M_ME_NA.)