104S
♦
ProLinx Gateway
Configure the Gateway
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 35 of 157
January 22, 2010
2.9 [M_ME_NB_1
104]
This section defines the monitored measured value, scaled database for the server
device emulated. This information is sourced from the database and is transferred to
the remote client unit. To determine the IOA (Information Object Address) for each
object, add the Point # (IOA) to the
M_ME_NB Parameter Offset
parameter value as
entered in the
[IEC-870-5-104 Database]
section.
This section takes the following parameters:
Point
#:
DB
Address:
Group(s):
Default
Deadband:
IV DB Bit
Each point is one, 16-bit word and the DB Address value corresponds to the word
offset in the gateway memory database. For additional information on how to set
these parameters, see the 104S Tutorial and Reference chapters of this manual.
2.10 [M_ME_NC_1
104]
This section defines the monitored short-float point database for the slave device
emulated. This information is sourced from the database and is transferred to the
remote client unit. To determine the IOA (Information Object Address) for each
object, add the Point # (IOA) to the
M_ME_NC Parameter Offset
parameter value as
entered in the
[IEC-870-5-104 Database]
section.
This section takes the following parameters:
Point
#
DB
Address
Groups
Default
Deadband
IV DB Bit
Each point is two, 16-bit words and the DB Address value corresponds to the
double-word offset in the gateway memory database. For additional information on
how to set these parameters, see the 104S Tutorial and Reference chapters of this
manual.
For a list of Group Codes, refer to the section on Group Codes (page 40).