104S
♦
ProLinx Gateway
Reference
(Firmware v3.00 and later)
Protocol Manual
ProSoft Technology, Inc.
Page 127 of 157
January 22, 2010
Status Register Name
Description
10211
Socket Close Count
(socket 0)
This word contains the number of times an active
close function executed.
10212
Socket Connect Count
(socket 0)
This word contains the number of times a
connection was established with the remote host
unit.
10213
…
10222
Host IP Address
(socket 0)
IP address of the client connected to the server.
10223
StartDT active (socket 0)
This word contains the current StartDT state as
follows:
0 = The gateway has not received the most recent
STARTDT request through this socket or there has
been no communication with the remote host unit.
1 = The gateway has received the most recent
STARTDT request through this socket (therefore
will be reporting data to the remote client
connected through this socket),
10223
…
10249
No Valid Data (socket 0)
Not Used.
10250
Socket State Value
(socket 1)
This word contains the current socket state as
follows:
-1 = Open Socket
0 = Wait for connection
1 = Transmit message if ready
2 = Receive packet and process message
3 = Process multiple messages in packet
50 = Send TestFr Act
51 = Wait for TestFr Con
60 = Send sequence (S-Format) message
1000 = Close Socket
1001 = Wait for socket to close
10251 Socket
Open
Count
(socket 1)
This word contains the number of times the socket
listen function executed.
10252
Socket Close Count
(socket 1)
This word contains the number of times an active
close function executed.
10253
Socket Connect Count
(socket 1)
This word contains the number of times a
connection was established with the remote host
unit.
Summary of Contents for ProLinx 104S