![ProSoft ProLinx 104S Protocol Manual Download Page 18](http://html1.mh-extra.com/html/prosoft/prolinx-104s/prolinx-104s_protocol-manual_1618885018.webp)
Configure the Gateway
104S
♦
ProLinx Gateway
Protocol Manual
(Firmware v3.00 and later)
Page 18 of 157
ProSoft Technology, Inc.
January 22, 2010
t1 Timeout Set Value
1
to
255
This is the timeout of send or test ASDUs and is in units of seconds. After a packet is
sent from the unit, the client must acknowledge the packet within this time interval or
else the unit will close the connection.
t2 Timeout Set Value
1
to
255
This is a timeout of when to send an S-format message to the host to acknowledge
outstanding messages received. This parameter is in units of seconds and must be
less than the value set for t1.
t3 Timeout Set Value
1
to
255
This is the timeout to wait on an idle line before the unit will send a TestFr.Act
message. This value is in units of seconds.
k (maximum queue)
1
to
20
This parameter specifies the number of unacknowledged messages the unit will
buffer. This parameter must match that in the host. If the set number of buffers are
filled in the unit, no other messages will be sent until the host unit acknowledges
some or all the messages.
w (latest ack threshold)
1
to
20
This parameter must match that of the host unit and specifies the number of
messages the gateway will receive before sending an S-format sequence
acknowledge message when no I-format data is ready to send. It is recommended to
set this value to 2/3 the value of k.
Summary of Contents for ProLinx 104S
Page 4: ......