MVI56E-MNETCR ♦ ControlLogix Platform
Diagnostics and Troubleshooting
Modbus TCP/IP Multi-Client Enhanced Communications Module for Remote Chassis
User Manual
ProSoft Technology, Inc.
Page 99 of 161
4.3.2 Configuration Error Word
The
Configuration Error Word
contains Client configuration error indications, in a
bit-mapped format. Specific bits in the module's
Configuration Error Word
are
turned on (set to 1) to indicate various configuration errors. The
Configuration
Error Word
appears in the
MNETCR.STATUS.ClientStatus[x]
controller tag array.
Bits set to 1 in the
Configuration Error Word
indicate the following errors.
Bit
Description
Hex Value
0
Reserved - not currently used
0001h
1
Reserved - not currently used
0002h
2
Reserved - not currently used
0004h
3
Reserved - not currently used
0008h
4
Invalid retry count parameter
0010h
5
The float flag parameter is not valid.
0020h
6
The float start parameter is not valid.
0040h
7
The float offset parameter is not valid.
0080h
8
The ARP Timeout is not in range (ARP Timeout parameter 0 or
greater than 60000 milliseconds) and will default to 5000
milliseconds.
0100h
9
The Command Error Delay is > 300 and will default to 300.
0200h
10
Reserved - not currently used
0400h
11
Reserved - not currently used
0800h
12
Reserved - not currently used
1000h
13
Reserved - not currently used
2000h
14
Reserved - not currently used
4000h
15
Reserved - not currently used
8000h
Combinations of errors will result in more than one bit being set in the error word.
Correct any invalid data in the configuration for proper module operation. A value
of zero (0) in this word indicates all bits are clear, which means that all module
configuration parameters contain valid values. However, this does not mean that
the configuration is valid for the user application. Make sure each parameter is
set correctly for the intended application.
4.3.3 Client Command Errors
There are several different ways to view Client Command Errors.
In the
MNETCR.STATUS.CmdErrorList
controller tag array
On the Client status data screens in the
ProSoft Configuration Builder
Diagnostics
At a module database location specified by the configuration's
MNET Client x
Command Error Pointer
, if the
Command Error Pointer
is enabled. This
means that the first register refers to command 1 and so on.