MVI56E-MNETCR ♦ ControlLogix Platform
Diagnostics and Troubleshooting
Modbus TCP/IP Multi-Client Enhanced Communications Module for Remote Chassis
User Manual
ProSoft Technology, Inc.
Page 101 of 161
Command List Entry Errors
Code
Description
-40
Too few parameters
-41
Invalid enable code
-42
Internal address > maximum address
-43
Invalid node address (<0 or >255)
-44
Count parameter set to 0
-45
Invalid function code
-46
Invalid swap code
-47
ARP could not resolve MAC from IP (bad IP address, not part of a
network, invalid parameter to ARP routine).
-48
Error during ARP operation: the response to the ARP request did
not arrive to the module after a user-adjustable ARP Timeout.
Note: When the Client gets error -47 or -48, it uses the adjustable ARP Timeout parameter in the
configuration file to set an amount of time to wait before trying again to connect to this non-existent
server. This feature allows the Client to continue sending commands and polling other existing
servers, while waiting for the non-existent server to appear on the network.