MVI56E-MNETCR ♦ ControlLogix Platform
Configuring the MVI56E-MNETCR Module
Modbus TCP/IP Multi-Client Enhanced Communications Module for Remote Chassis
User Manual
ProSoft Technology, Inc.
Page 65 of 161
To use the CIPconnect Path Editor, follow these steps.
1
Configure the path between the 1756-ENBT connected to your PC and the
MVI56E-MNETCR module.
o
If the module is located in a remote rack, add more racks to configure the
full path.
o
The path can only contain ControlNet or Ethernet/IP networks.
o
The maximum number of supported racks is six.
2
Click
C
ONSTRUCT
CIP
P
ATH
to build the path in text format
3
Click
OK
to confirm the configured path.
Example 1: Local Rack Application
For this example, the MVI56E-MNETCR module is located in the same rack as
the 1756-ENBT that is connected to the PC.
Ethernet
Rack 1
MVI56E Module
1756-ENBT
0
1
2
3
Rack 1
Slot
Module
Network Address
0
ControlLogix Processor
-
1
Any
-
2
MVI56E-MNETCR
-
3
1756-ENBT
IP=192.168.0.100