34
Contents
Appendix C — Peer Cop Example
The Host PLC (984) must also have its dip switches set to Node Address
7 and a proper Modbus Plus cable connected between the PLC and the
1560-MBP.
Configuration Extension Blocks
This section is a PLC printout (using Modsoft) that shows how the PLC’s
Peer Cop is configured.
PEER COP
Timeout : 500 ms Total Links:1 Link Id:1 - Internal
On Error : CLEAR USED 20 OF 512 WORDS
Access to Node : 6
MODE REFERENCE LEN TYPE INDEX
SPECIFIC INPUT -
SPECIFIC OUTPUT -
GLOBAL INPUT 100001-100016 1 1
GLOBAL INPUT 400200-400208 9 BIN 2
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
TO ALL NODES ON LINK
GLOBAL OUTPUT 400100-400131 32 BIN
The 1560 MBP-1560 Dip Switch 2 Configuration is as follows:
Switch Position Description
1
On
Set the 1560-MBP Node Address 6
2
Off
3
On
4
Off
5
Off
6
Off
7
On
Enable Global Data Control from a host. Allows
the Control and Reference words to be
obtained from the Host PLC Global Data Block
8
On
Enables Drive fault on loss of Mobus Plus
communication