EX500-TF2Z180EN

 

Page 1 of 2 

 

Instruction Manual 

Gateway unit – PROFINET compatible 

Series EX500-GPN2

 

 

The intended use of the Gateway unit is for connection to SI units and 
input devices for the control of pneumatic valves.

 

1 Safety Instructions 

These safety instructions are intended to prevent hazardous situations 
and/or equipment damage. These instructions indicate the level of 
potential hazard with the labels of “Caution,” “Warning” or “Danger.” 
They are all important notes for safety and must be followed in addition 
to International Standards (ISO/IEC)

 *1)

, and other safety regulations. 

*1)

 ISO 4414: Pneumatic fluid power - General rules relating to systems. 

ISO 4413: Hydraulic fluid power - General rules relating to systems. 
IEC 60204-1: Safety of machinery - Electrical equipment of machines. 
(Part 1: General requirements) 
ISO 10218-1: Manipulating industrial robots -Safety. etc. 

  Refer to product catalogue, Operation Manual and Handling 

Precautions for SMC Products for additional information. 

  Keep this manual in a safe place for future reference. 

 

Caution 

Caution indicates a hazard with a low level of risk which, if 

not avoided, could result in minor or moderate injury. 

 

Warning 

Warning indicates a hazard with a medium level of risk 

which, if not avoided, could result in death or serious injury. 

 

Danger 

Danger indicates a hazard with a high level of risk which, if 

not avoided, will result in death or serious injury. 

Warning 

 

Always ensure compliance with relevant safety laws and 
standards. 

  All work must be carried out in a safe manner by a qualified person in 

compliance with applicable national regulations. 

 

  Refer to the operation manual on the SMC website (URL: 

https://www.smcworld.com

) for more Safety instructions. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

2 Specifications 

General specifications 

Item 

Specifications 

Ambient operating temperature 

-10 to +50 

o

Ambient humidity range 

35 to 85% RH (no condensate) 

Ambient storage temperature  

-20 to +60 

o

Withstand voltage 

1000 VAC applied for 1 minute 

Insulation resistance 

500 VDC, 2 M

Ω

 or more 

Weight 

550 g 

Electrical specifications 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

3 Name and function of parts 

 

 

 

No 

Part 

Description 

1  Port1 / IN connector 

Connection to PROFINET line. 

2  Port2 / OUT connector 

3  Power supply connector 

Connection for power supply. 

4  Branch port A (COM A) 

Connection to SI units (with manifold 
valves) or input units using a branch 
cable. 

5  Branch port B (COM B) 

6  Branch port C (COM C) 

7  Branch port D (COM D) 

8  LED Display 

Displays the unit status. 

9  Protective cover 

Cover should not be opened. 

10  FE terminal (M3) 

Functional Earth (FE). 

 

4 Installation 

4.1  Direct mounting 

Secure in position using 4 x M5 screws, 15 mm minimum thread length. 

 

4.2  Wiring connections 

 

Communication Connector 

Select the appropriate Ethernet  cables to mate with the connectors 
on the SI unit. The PROFINET connection has 2 ports, PORT 1 and 
PORT 2, and both ports can be used for connection. 

M12 4-pin Socket (D-coded) 

Connector 

Pin No. 

Signal name 

PORT 1 / PORT 2 

 

TX+ 

RX+ 

TX- 

RX- 

 

 

Power Supply Connector 

Connect the power supply to the power supply connector on the 
Gateway unit. With this cable, power is supplied to the output devices 
(such as solenoid valve) and the input devices and for control. 

 

 

 
 
 
 
 

 

  Both single and two power supply systems can be adopted, however 

the wiring should be made separately (for solenoid valves / outputs 
and for input and control) for either system. 

The M12 connector cable has two types, Standard M12 and 
SPEEDCON compatible. If both plug and socket have SPEEDCON 
connectors, the cable can be inserted and connected by turning it a 
1/2 rotation.  
A standard connector can be connected to a SPEEDCON connector. 

 

 

Branch Connector 

Connect  SI units (solenoid valves)  and input devices  to  the  Branch 
port  connectors  (COM  A  -  D)  using  an  M12  (8-pin)  connector cable 
(EX500-AC###-S#P#). 
As each cable contains power supply wiring, there is no need to 
supply power to the SI unit (solenoid valves)  or input devices 
separately. 

 

Warning 

  Be sure to fit a seal cap (EX9-AWTS) on any unused connectors. 

Proper use of the seal cap enables the enclosure to maintain IP65 
specification. Tightening torque: 0.1 N•m. 

4.3  Ground Connection 

  Connect the FE terminal (M3) to ground. 

  Individual grounding should be provided close to the product with a 

short cable to assure the safety and noise resistance of the system. 

  Resistance to ground should be 100 

Ω 

or less. 

4 Installation (continued) 

4.4  Environment 

Warning 

  Do not use in an environment where corrosive gases, chemicals, salt 

water or steam are present. 

  Do not install in a location subject to vibration or impact in excess of 

the product’s specifications.  

  Do not mount in a location exposed to radiant heat that would result 

in temperatures in excess of the product’s specifications. 

 

5 Setting 

5.1  Hardware Configuration 

An applicable GSDML file is required to configure the Gateway unit for 
the PROFINET network.  
Download the latest GSDML  file from the SMC website (URL: 

https://www.smcworld.com

). 

Model 

GSDML and Symbol files 

EX500-GPN2 

GSDML-V2.3-SMC-EX500-

∗∗∗∗∗∗∗∗

.xml 

GSDML-0083-000B-EX500_N.bmp 

 
Technical documentation giving detailed configuration information can 
be found in the operation manual on the SMC website  (URL: 

https://www.smcworld.com

)

 

 

 

 

 

 

 

6 LED Display 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 

ORIGINAL INSTRUCTIONS 

Item 

Specifications 

Power supply voltage 

Control and Input: 24.0 VDC ±10% 

Solenoid valves: 24.0 VDC +10% / -5% 

Rated Current 

Power supply for control and input: 6.2 A 
(GW current consumption: 200 mA max.). 
Power supply for solenoid valve: 4 A 

Number of Inputs / Outputs 

128 Inputs / 128 Outputs 

Communication specifications 

Item 

Specifications 

Protocol 

Ethernet (IEEE802.3) 

Communication media 

100BASE-TX (Cat5 or more) 

Communication speed 

100 Mbps 

Communication method 

Full Duplex / Half Duplex (auto. selected) 

Fieldbus protocol 

PROFINET IO 

Device Information 

Vendor ID: 0x0083 (SMC Corporation) 

Device ID: 0x000B 

Low level bus specifications 

Item 

Specifications 

Number of inputs / outputs 

128 Inputs / 128 Outputs 

Applicable system 

Gateway distribution system 2 (128 point) 

Number of branch ports 

4 (input: Max. 32 points / Output: Max. 32 

points per branch) 

Number of connected slaves 

16 max. (input unit: 2 pcs. / SI unit: 2 pcs. 
per branch) 

Power supply for control and input   24 VDC, Max. 1.5 A per one branch port 

Power supply for Solenoid valve  

24 VDC, Max. 1.0 A per one branch port 

Branch cable length 

Total length 20 m or less per branch 

 

7/8 inch, 5-pin Plug 

Connector 

Pin No. 

Signal name 

 

0 V (solenoid valves) 

0 V (control and input) 

FE 

24 VDC (control and input) 

24 VDC (solenoid valves) 

 

 

 

 

  Gateway unit status 

LED 

Description 

SF 

OFF 

Normal operation 

Red ON 

Diagnostics error 

BF 

OFF 

PROFINET communication established 

Red flashing  PROFINET communication not established 

Red ON 

No Link (Port1 / Port2) 

PWR 

OFF 

Power supply for control and inputs is OFF 

Green ON  Power supply for control and inputs is ON 

PWR(V) 

OFF 

Power supply for solenoid valves is OFF 

Green ON  Power supply for solenoid valves is ON 

L/A1 

OFF 

No Link, No Activity (Port1) 

Green ON  Link, No Activity (Port1) 

Orange 

flashing 

Link, Activity (Port1) 

L/A2 

OFF 

No Link, No Activity (Port2) 

Green ON  Link, No Activity (Port2) 

Orange 

flashing 

Link, Activity (Port2) 

 