Contents
MVI69-GEC ♦ CompactLogix or MicroLogix Platform
User Manual
Page 22 of 86
ProSoft Technology, Inc.
February 18, 2014
2
Click the
[+]
sign next to any
icon to view module information and configuration
options.
3
Double-click any
icon to open an
Edit
dialog box.
4
To edit a parameter, select the parameter in the left pane and make your changes in the
right pane.
5
Click
OK
to save your changes.
Printing a Configuration File
1
In the main PCB window, right-click the
M
ODULE
icon and choose
V
IEW
C
ONFIGURATION
.
2
In the
View Configuration
dialog box, open the
F
ILE
menu, and choose
P
RINT
.
3
In the
dialog box, choose the printer to use from the drop-down list, select the
printing options, and then click
OK
.
2.2
[Module]
This section of the file describes the database setup and module level parameters.
[Module]
Module Name: MVI69-GEC Communication Module DEFAULT
0
to
80
characters
Specifies a name to identify the module and the configuration file.
2.3
[Server x]
You can configure up to five servers ([Server 0] through [Server 4]). The configuration
section for each server contains the same set of parameters. You can configure the
parameters for each server to meet the requirements of your application.
2.3.1 Enabled
Yes or No
This parameter determines if the server will be utilized by the module. If a value of "Yes" is
entered, the server will be used. Any other value will disable the server.
2.3.2 Service Port Number
1 to 65535
This parameter sets the TCP/IP service port for this server. Each server can have its own
unique service port or can share the same number with other servers.
2.3.3 Connection Timeout
0 or 5000 to 65535
This parameter specifies the number of milliseconds the server will permit the server to be
inactive after a connection is made before closing the socket. This timeout period is reset on
each read or write packet. If the parameter is set to 0, the connection will not timeout.