MVI56-HART ♦ ControlLogix Platform
Ladder Logic
HART Multi-drop Master Communication Module
User Manual
ProSoft Technology, Inc.
Page 57 of 171
October 13, 2011
3.2
Adding the Module to an Existing Project
1
Select the
I/O Configuration
folder in the
Controller Organization
window of RSLogix
5000, and then click the right mouse button to open a shortcut menu. On the shortcut
menu, choose
N
EW
M
ODULE
.
This action opens the
Select Module
dialog box:
2
Select the
1756-M
ODULE
(G
ENERIC
1756
M
ODULE
)
from the list and click
OK
. This
action opens the
New Module
dialog box.
3
Enter the
Name, Description
and
Slot
options for your application. You must select
the
Comm Format
as
D
ATA
-
INT
in the dialog box, otherwise the module will not
communicate. Click
OK
to continue.
Parameter
Value
Name
Enter a module identification string. Example:
HART_2