Configuring the MVI56-HART Module
MVI56-HART ♦ ControlLogix Platform
User Manual
HART Multi-drop Master Communication Module
Page 34 of 171
ProSoft Technology, Inc.
October 13, 2011
2.2
MVI56-HART Configuration File
The configuration file for MVI56-HART consists of the following sections.
Section
Description
[MODULE]
General module level parameters
[HART PORT 0]
HART Port (Channel) 0 configuration parameters
[HART PORT 0 COMMANDS]
HART command list for Port (Channel) 0
[HART PORT 1]
HART Port (Channel) 1 configuration parameters
[HART PORT 1 COMMANDS]
HART command list for Port (Channel) 1
2.2.1 [MODULE]
The [Module] section contains the data that applies to the whole module and includes the
backplane data transfer parameters.
Module Name
0
to
80
characters
This parameter assigns a name to the module that can be viewed using the
configuration/debug port. Use this parameter to identify the module and the configuration
file.
Read Register Start
0
to
3999
This parameter specifies the starting register address of a block of data registers to
transfer from the module to the processor. This will be used for data brought into the
processor from other nodes on the network.
Write Register Count
0
to
4000
This parameter specifies the number of registers to transfer from the processor to the
module.
Write Register Start
0
to
3999
This parameter specifies the starting register address of a module register block where
data transferred from the processor will be stored. This will be used for data to be sent
from the processor to other nodes on the network.
Write Register Count
Range 0 to 4000
This parameter specifies the number of registers to transfer from the processor to the
module. Valid entry for this parameter is 0 to 4000.