MVI56-DNP
♦
ControlLogix Platform
Reference
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 151 of 171
July 21, 2011
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
2
Time Delay Fine
129
07, With
Quant=1
16
Master will process this
variation for propagation delay
calculation
60
0
Not Defined
Not Defined in DNP
1
Class 0 Data
1
06
Master will generate this
variation
2
Class 1 Data
1
06, 07,
08
Master will generate this
variation
3
Class 2 Data
1
06, 07,
08
Master will generate this
variation
4
Class 3 Data
1
06, 07,
08
Master will generate this
variation
70
0
Not Defined
1
File Identifier
80
0
Not Defined
1 Internal
Indications 2 00,
Index=7
24
The Master will generate this
variation
81
0
Not Defined
1
Storage Object
82
0
Not Defined
1
Device Profile
83
0
Not Defined
Not Defined in DNP
1 Private
Registration
Object
2 Private
Registration
Objection Descriptor
90
0
Not Defined
Not Defined in DNP
1
Application Identifier
100 0
1
Short Floating Point
48
2
Long Floating Point
80
3
Extended Floating
Point
88
101 0
1
Small Packed Binary-
Coded Decimal
16
2
Medium Packed
Binary-Coded Decimal
32
3
Large Packed Binary-
Coded Decimal
64
No Object
13
Master supports the Cold
Restart Function
14
Master supports the Warm
Restart Function
20
Master supports the Enable
Unsolicited Function