MVI56-DNP
♦
ControlLogix Platform
Reference
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 145 of 171
July 21, 2011
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
52
0
Time Delay - All
Variations
1
Time Delay Coarse
129
07, With
Quant=1
16
Slave will never return this
variation
2
Time Delay Fine
129
07, With
Quant=1
16
Slave will return this variation
to functions 0D, 0E, and 17
60
0
Not Defined
Not Defined in DNP
1
Class 0 Data
1
06
Slave will respond to this
variation with all static data
2
Class 1 Data
1
06, 07,
08
Slave will respond to this
variation (No class 1 data
defined in application)
3
Class 2 Data
1
06, 07,
08
Slave will respond to this
variation with all class 2 data
(binary input events)
4
Class 3 Data
1
06, 07,
08
Slave will respond to this
variation with all class 3 data
(analog input events)
70
0
Not Defined
Not Defined in DNP
1
File Identifier
Slave will return Unknown
Object to this request
80
0
Not Defined
Not Defined in DNP
1 Internal
Indications
2 00,
Index=7
24
Slave will respond to this
variation
81
0
Not Defined
Not Defined in DNP
1
Storage Object
82
0
Not Defined
Not Defined in DNP
1
Device Profile
83
0
Not Defined
Not Defined in DNP
1 Private
Registration
Object
2 Private
Registration
Objection Descriptor
90
0
Not Defined
Not Defined in DNP
1
Application Identifier
100 0
1
Short Floating Point
48
2
Long Floating Point
80
3
Extended Floating
Point
88
101 0
1
Small Packed Binary-
Coded Decimal
16
2
Medium Packed
Binary-Coded
Decimal
32
3
Large Packed Binary-
Coded Decimal
64