MVI56-DNP
♦
ControlLogix Platform
Reference
DNP 3.0 Server
User Manual
ProSoft Technology, Inc.
Page 141 of 171
July 21, 2011
OBJECT REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
21
0
Frozen Counter - All
Variations
1
06
32
Slave will return variation 9
data
1 32-Bit
Frozen
Counter
129, 130 00, 01
40
Slave will return Unknown
Object to this request
2 16-Bit
Frozen
Counter
129, 130 00, 01
24
Slave will return Unknown
Object to this request
3
32-Bit Frozen Delta
Counter
40
Slave will return Unknown
Object to this request
4
16-Bit Frozen Delta
Counter
24
Slave will return Unknown
Object to this request
5 32-Bit
Frozen
Counter With Time Of
Freeze
88
Slave will return Unknown
Object to this request
6 16-Bit
Frozen
Counter With Time Of
Freeze
72
Slave will return Unknown
Object to this request
7
32-Bit Frozen Delta
Counter With Time Of
Freeze
88
Slave will return Unknown
Object to this request
8
16-Bit Frozen Delta
Counter With Time Of
Freeze
72
Slave will return Unknown
Object to this request
9 32-Bit
Frozen
Counter Without Flag
1
06
129, 130 00, 01
32
Slave will return this variation
10
16-Bit
Frozen
Counter Without Flag
1
06
129, 130 00, 01
16
Slave will return this variation
(counter upper 16-bits
removed)
11
32-Bit Frozen Delta
Counter Without Flag
32
Slave will return Unknown
Object to this request
12
16-Bit Frozen Delta
Counter Without Flag
16
Slave will return Unknown
Object to this request
22 0 Counter
Change
Event - All Variations
1 06,
07,
08
Slave will parse this request
and return no data
1 32-Bit
Counter
Change Event
Without Time
129, 130 17, 28
40
Slave will return Unknown
Object to this request
2 16-Bit
Counter
Change Event
Without Time
129, 130 17, 28
24
Slave will return Unknown
Object to this request
3
32-Bit Delta Counter
Change Event
Without Time
40
Slave will return Unknown
Object to this request
4
16-Bit Delta Counter
Change Event
Without Time
24
Slave will return Unknown
Object to this request
5 32-Bit
Counter
Change Event With
Time
88
Slave will return Unknown
Object to this request