MVI56-CAS
♦
ControlLogix Platform
Reference
Teledyne CA Slave Module
Page 66 of 86
ProSoft Technology, Inc.
December 26, 2007
Group Register
Content
Description
5011
Baud
Rate
This is the baud rate to be used on the port. Enter the
baud rate as a value. For example, to select 19K baud,
enter 19200. Valid entries for this field include 110, 150,
300, 600, 1200, 2400, 4800, 9600, 19200, 28800, 38400,
57600, and 115.
5012
Parity
This is the parity code to be used for the port. None, Odd,
Even.
5013
Data
Bits
This parameter sets the number of data bits for each word
used by the protocol. Valid entries are 5 or 8.
5014
Stop
Bits
This parameter sets the number of stop bits to be used
with each data value set. Valid entries are 1 and 2.
5015
RTS
On
This parameter sets the number of milliseconds to delay
after RTS is asserted before the data is transmitted. Valid
values are 0 to 65535.
5016
RTS
Off
This parameter sets the number of milliseconds to delay
after the last byte of data is sent before the RTS modem
signal will be set low. Valid values are 0 to 65535.
5017
Minimum
Response
Time
This parameter specifies the minimum number of
milliseconds to delay before responding to a request
message. This pre-send delay is applied before the RTS
on time. This may be required when communicating with
slow devices.
5018
Use CTS
Line
This parameter specifies if the CTS modem control line is
to be used. If the parameter is set to 0, the CTS line will
not be monitored. If the parameter is set to 1, the CTS line
will be monitored and must be high before the module will
send data. This parameter is normally only required when
half-duplex modems are used for communication (2-wire).
5019
Slave
ID
This parameter defines the virtual slave address for the
internal database. Any request received by the port with
this address will be processed by the module. Be certain
each device has a unique address on a network. Valid
range for this parameter is 1 to 255 (247 on some
networks).
5020
Use Guard
Band
Not implemented.
5021
Guard
Band Time
Not Implemented.
5022
Direct
Control
This parameter enables direct control. If enabled, a Select
command is not required before a Control command.
Valid entries are 0 and 1.
5023
Swap
Config
This parameter sets the data swapping. The swapping is
set as a bit field. Bit 0 corresponds to status data, Bit 1 to
analog data, and Bit 2 to meter data.