Module Configuration
MVI46-N2
♦
SLC Platform
Johnson Controls N2 Communication Module
ProSoft Technology, Inc.
Page 25 of 68
October 27, 2008
2.3.3 [N2
Config]
This section is used to define the N2 configuration data.
Binary Input Object Count
0 to 960
Determines the number of Binary Input Objects available
Analog Input Object Count
0 to 300
Determines the number of Analog Input Objects available.
Binary Output Object Count
0 to 960
Determines the number of Binary Output Objects available.
Analog Output Object Count
0 to 300
Determines the number of Analog Output Objects available.
2.3.4 [N2 Port x]
This section is used to define the port configuration for the N2 device
Enable
Yes or No
This parameter specifies whether to enable or disable the port. No = Port
Disabled, Yes = Port Enabled.
Slave Address
0 to 255
This parameter defines the Slave Node Address for the internal database. All
requests received by the port with this address are processed by the module.
Verify that each device has a unique address on a network. Valid range for this
parameter is 0 to 255.
Baud Rate
300 to 115200
This parameter specifies the baud rate to be used on the port. Valid values are
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200.