Restricted Operating Menu / Description
General Settings
Possible values
Initial value
Increment
Lower value
Upper value
Remarks
Setpoint
750 mV
1 mV
lower limit
upper limit
2 setpoints necessary
measuring range measuring range
for control with dead zone.
Setpoint 2 > setpoint 1
Control parameter xp
10 %
1 %
1 %
500 %
xp referred to measuring range
Control parameter Ti
off
1 s
1 s
9999 s
Function off = 0 s
Control parameter Td
off
1 s
1 s
2500 s
Function off = 0 s
Manual metering
0 %
1 %
-100 %
+100 %
Possible values
Initial value
Increment
Lower value
Upper value
Remarks
Alarm relay
active
active
not active
Access code
5000
1
1
9999
Language
as per identity
as per identity
code
code
Operating menu
restricted
restricted
complete
D1C2-016-GB
Access to all setting menus can be blocked with an access code !
general setting
information
ident-code: D1CA
software version
DxRxxxxxxxxxx
D1C-A1 FW-5.00
alarm relay
access c.:
=
=
operating menu:
active
5000
english
restricted
Abbreviations for control variables:
x
p
= 100 %/Kp (inverse proportional coefficient)
T
i
= I controller integration time [s]
T
d
= D controller differential time [s]
Access Code
Access to the setting menu can be prevented by setting up an access code. The DULCOMETER
®
D1C
controller is supplied with the access code 5000 which permits free access to the setting menu. The
calibration menu remains freely accessible even if access to the setting menu is blocked by the code.