11
Technical data
Tab. 6: Technical data
Parameter
Unit
Type
Type
Type
Capacity per hour (h)
g/h
100
200
300
Capacity per day (d)
kg/d
2.2
4.4
6.6
Dimensions
LxWxH of frame
mm
2225x610x1510
Space requirement
mm
1800x1500
Transport weight
kg
750
Transport box
mm
2815x1015x2340
Brine tank
l
200
Recommended volume of the product tank
(1 day’s production)
l
500 ... 1000
Separating tank
l
200
Process data
Number of cell chambers
Qty.
1
2
3
Water needed*
l/h
250
500
750
Salt per day (d)
kg/d
4.4
8.8
13.2
Fan vent **
m³/h
200
Product concentration
mg/l
± 400
Electrical data
Electrical voltage (50 Hz)
230 VAC/1P/N/PE
Power consumption (net)
kVA
1.1
1.5
1.9
Fuse
A
C25A, 1P, N
Connectors
Water supply
mm
20
Brine for membrane cell
mm
20
Brine tank filling level
mm
20
Ventilation line
mm
20
Brine for softener
mm
20
DULCO
®
Lyt
mm
20
Fan bleed ****
mm
63
Process water
mm
32
Fill separating tank
mm
20
Drain
mm
50
Drain
mm
20
Remarks
* only use softened water for regeneration.
** provide a fan for dilution to 0.4 % of the lower explosion limit
Technical data
62