Check whether the O-ring on the retaining fixture for the protective tube is fitted in the groove
and is not damaged, replace damaged seal.
Insert the new lamp in the protective tube and leave protruding by approx. 100 mm
Plug in connector on UV lamp
Systems with connector on UV lamp cover
Switch off UV disinfection system with the START/STOP button
Switch off master switch or disconnect power plug
Close shut-off valves upstream and downstream of the radiation chamber
Release circular plug on lamp cover by turning the knurled nut and disconnect
Release knurled nut on retaining fixture for lamp protective tube and detach
Lift lamp cover and completely remove UV lamp
Unplug UV lamp from connector and place to one side
Plug in connector at new UV lamp
The connector can be plugged in only in certain positions, it may be necessary to turn it
through 90
before attempting to plug in again
Check whether the O-ring on the retaining fixture for the protective tube is fitted in the groove
and is not damaged, replace damaged seal.
Insert new UV lamp into protective tube until the UV lamp cover comes to rest against the
retaining fixture for the protective tube
Secure UV lamp cover on retaining fixture for protective tube with knurled nut. Use only very
little force to tighten the knurled nut.
Plug in circular connector at the socket on the UV lamp cover and secure with knurled nut.
Use only very little force to tighten the knurled nut.
IMPORTANT!
The connector can be plugged in only in certain positions, it may be necessary to turn it
through 90
before attempting to plug in again.
Completely insert the UV lamp into the protective tube
Secure lamp cover to retaining fixture for protective tube with knurled nut;
hand-tighten knurled nut
Slowly open shut-off valve upstream of radiation chamber
Open shut-off valve downstream of radiation chamber
(necessary only for manual shut-off valve)
Switch on master switch or connect power plug
Reset lamp operating hours
With the system switched off press the CHANGE key to display the lamp operating hours
and switching operations
and switching operations
Confirm by pressing the ENTER key – “Enable Code Query” appears in the display
Enter the enable code and confirm by pressing the ENTER key – “Reset” appears in the
display
Confirm by pressing the ENTER key – the display is now reset
ATTENTION!
Recalibrate the UV-C sensor after installing new UV lamps!
Safe and reliable operation of the UV disinfection system is guaranteed only after
recalibration.
7.3
Calibrating UV-C Sensor
The UV-C sensor is calibrated at the factory and does not need recalibration.
IMPORTANT!
• Observe the supplementary instructions for special applications, in which the sensor
signal is displayed in %.
• All new UV lamps require a burn-in period of 100 to 200 hours. Therefore, check the
safety threshold and the warning threshold approximately 200 operating hours after
replacing the UV lamps.