Assembly and Installation
Please take note of the following safety information prior to installation:
WARNING!
Make sure that
• the maximum permissible water flow rate is not exceeded and
• the UV transmission does not drop below the minimum permissible levels
otherwise adequate disinfection will no longer be guaranteed!
The maximum permissible water flow rate is defined in the supplied datasheet.
It is an integral function of the required radiation exposure level and of the minimum permissible
UV transmission of the water to be disinfected.
ATTENTION!
• The place of installation must be dry and frost-free while ensuring the UV disinfection
system is protected from the effects of chemicals, dyeing agents and vapours.
• The ambient temperature and the radiation temperature in the immediate vicinity must
not exceed 40
C!
• If the water to be disinfected contains solid particles or turbidity substances, a suitable
filter should be installed upstream of the UV disinfection system.
• Make sure that the maximum permissible operating pressure as defined in the datasheet
is not exceeded.
IMPORTANT!
Despite the use of modern lamp ballasts with protective lamp ignition, the UV system
should be operated such as to avoid frequently switching the UV lamps on and off.
5.1
Radiation Chamber
The design of the radiation chamber is defined in the datasheet provided:
Vertical wall-mounted, reclined
or
upright
versions
.
5.1.1
Installation
ATTENTION!
• Only the type of installation defined in the datasheet is permitted.
• Leave sufficient space for maintenance and servicing work!
The necessary clearance is defined in the datasheet provided.
Vertical wall mounting
Using the installation material provided, secure the radiation chamber vertically on a wall or a
suitable frame.
Reclined/horizontal
Using the installation material provided, secure the radiation chamber horizontally on a wall or
a suitable frame.
Upright
Install radiation chamber on the floor.
5.1.2
Affixing Warning Sign
IMPORTANT!
Affix the supplied self-adhesive warning sign such that it is clearly visible on the radiation
chamber.