Programming the Outputs
Page 81 of 102
Pay close attention to the plumbing layout in
Figure
35.
The direction of the pipes is not as
important as having the flashing controlled beyond
the sensor and blowdown valve!
Captured Sample is not recommended for
Pulse relays 6
–
9.
Choosing the captured sample routine and
setting the timers;
1- Press
MENU
2- Scroll down to I/O Setup and press OK
3- Scroll down to your blowdown valve and
press OK
4- Scroll down to Special Control and press
OK
5- Scroll down to Captured Sample and
press F1 SELECT.
6- Use the arrows to adjust the value if
necessary then press F2 Save when
done.
7- Adjust the Measure, blowdown and
resample values as needed. Press F2
Save to continue.
The Fail to Sample option is not currently
implemented.
The routine is set. Continue to use this menu to
edit the relay name, engineering units, decimal
digits, interlocks and blocks.