![Proline ADH10L Operating Instructions Manual Download Page 58](http://html1.mh-extra.com/html/proline/adh10l/adh10l_operating-instructions-manual_1614867058.webp)
–
Cylinders shall be kept upright.
–
Ensure that the refrigeration system is earthed prior to charging the system with refrigerant.
–
Label the system when charging is complete (if not already).
–
Extreme care shall be taken not to overfill the refrigeration system.
Prior to recharging the system, it shall be pressure tested with OFN. The system shall be leak tested on completion of charging but prior to commissioning. A
follow up leak test shall be carried out prior to leaving the site.
Decommissioning
Before carrying out this procedure, it is essential that the technician is completely familiar with the equipment and all its detail. It is recommended good
practice that all refrigerants are recovered safely. Prior to the task being carried out, an oil and refrigerant sample shall be taken in case analysis is required prior
to re-use of reclaimed refrigerant. It is essential that electrical power is available before the task is commenced.
a)
Become familiar with the equipment and its operation.
b)
Isolate system electrically.
c)
Before attempting the procedure ensure that:
mechanical handling equipment is available, if required, for handling refrigerant cylinders;
all personal protective equipment is available and being used correctly;
the recovery process is supervised at all times by a competent person;
recovery equipment and cylinders conform to the appropriate standards.
d)
Pump down refrigerant system, if possible.
e)
If a vacuum is not possible, make a manifold so that refrigerant can be removed from various parts of the system.
f)
Make sure that cylinder is situated on the scales before recovery takes place.
g)
Start the recovery machine and operate in accordance with manufacturer's instructions.
h)
Do not overfill cylinders. (No more than 80 % volume liquid charge).
i)
Do not exceed the maximum working pressure of the cylinder, even temporarily.
j)
When the cylinders have been filled correctly and the process completed, make sure that the cylinders and the equipment are removed from site promptly
and all isolation valves on the equipment are closed off.
k)
Recovered refrigerant shall not be charged into another refrigeration system unless it has been cleaned and checked.
Labelling
Equipment shall be labelled stating that it has been de-commissioned and emptied of refrigerant. The label shall be dated and signed. Ensure that there are
labels on the equipment stating the equipment contains flammable refrigerant.
Recovery
When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. Ensure that the correct number of
cylinders for holding the total system charge are available. All cylinders to be used are designated for the recovered refrigerant and labelled for that refrigerant
(i.e. special cylinders for the recovery of refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off valves in good working order.
Empty recovery cylinders are evacuated and, if possible, cooled before recovery occurs.
The recovery equipment shall be in good working order with a set of instructions concerning the equipment that is at hand and shall be suitable for the recovery
of flammable refrigerants. In addition, a set of calibrated weighing scales shall be available and in good working order. Hoses shall be complete with leak-free
disconnect couplings and in good condition. Before using the recovery machine, check that it is in satisfactory working order, has been properly maintained and
that any associated electrical components are sealed to prevent ignition in the event of a refrigerant release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery cylinder, and the relevant Waste Transfer Note arranged. Do not
mix refrigerants in recovery units and especially not in cylinders.
If compressors or compressor oils are to be removed, ensure that they have been evacuated to an acceptable level to make certain that flammable refrigerant
does not remain within the lubricant. The evacuation process shall be carried out prior to returning the compressor to the suppliers. Only electric heating to the
compressor body shall be employed to accelerate this process. When oil is drained from a system, it shall be carried out safely.
Summary of Contents for ADH10L
Page 8: ...EN 2 EN 7 EN 8...
Page 10: ...EN 4 Internal drying function Internal drying function...
Page 12: ...EN 6 0 If you wish to cancel the timer repeatedly press until the display shows 0 1 1 2 3 4 2...
Page 16: ...FR 10...
Page 17: ...FR 11 FR 17 FR 18...
Page 18: ...FR 12...
Page 20: ...FR 14 interne...
Page 25: ...FR 19 R290 40g 200W 220 240V 50Hz 1 1A 10L jour 2 8 0 8 Mpa 10 kg...
Page 26: ...FR 20 Ets Darty fils SAS 14 route d Aulnay 93140 Bondy France 24 01 2019...
Page 28: ...NL 22 NL 27 NL 28...
Page 30: ...NL 24 Interne drogingsfunctie...
Page 35: ...NL 29 R290 40g 200W 220 240V 50Hz 1 1A 10l dag 2 8 0 8 Mpa 10 kg...
Page 36: ...NL 30 Ets Darty fils SAS 14 route d Aulnay 93140 Bondy France 24 01 2019...
Page 38: ...ES 32...
Page 40: ...ES 34 interno Dep sito de agua...
Page 47: ...PT 41 PT 46 PT 47...
Page 49: ...PT 43 interna Dep sito est cheio 1...
Page 55: ......
Page 64: ......
Page 69: ......
Page 73: ......