Special functions
ON/OFF: 

The dosing station is not equipped with a power supply switch. To shut it

off, press the 

#

key for 4 seconds. OFF will be displayed on the screen.

Press the 

#

key for 4 seconds, to turn it on again.

REINITIALIZATION:

If you want to erase the memory with all data already entered,

calibration and password, you must proceed as follows:
1) Shut off the power supply.
2) Simultaneously press the 

# $

keys and connect to the power supply again while continuing

to press both keys.
3) Release the keys. The following message will be displayed: “CHECKSUN ERROR”. Press any key.
4) Proceed to the setup.

START: 

This function allows you to simultaneously turn on the two dosing pumps at maximum

frequence. The following procedure must be observed:
1) Shut off the power supply.
2) Simultaneously press the following keys 

! "

.Then connect to the power supply again while

continuing to press both keys.
3) Release the keys, the dosing station will remain in this mode, until the power supply will
discontinued.

The sensors must be calibrated during the installation procedure to obtain reliable measuring
values. Proceed in the following order: pH and then Redox (mV).

pH section

It takes two steps to calibrate the pH sensor using two buffered solutions.
Proceed only if you have provided for the following:

The buffered solutions must be available (pH 7 and pH 4).
Temperature must be known.
Attach the BNC connector of the pH sensor to the connector provided for this purpose.
Remove the protective cover of the sensor.
Clean with water, dry and immerse the sensor in the buffered pH 7 solution.
The sensor must be stirred and kept submerged.

Press the 

ENTER

key in the main menu for 3 seconds. Enter the password, if programmed,

and press 

ENTER

again. The following will be displayed:

ATTENTION :
THE DOSING STATION WILL QUIT THE PROGRAMMING MODE AND GO BACK TO
SCREEN 1 AFTER 90 SECONDS, UNLESS YOU HIT A KEY.

Screen 2

The cursor must remain on " . " SETUP. Then press 

ENTER

.

Screen 3

SENSOR CALIBRATION

%

Setup         
parameter

%

Set-Point        
Calibrate

Summary of Contents for REGUL SYSTEM

Page 1: ...EM automatic dosing and regulation station This is an efficient powerful and reliable product Prior to installation and utilisation the subsequent information must be read carefully It contains import...

Page 2: ......

Page 3: ...ALLATION DIAGRAM Page 7 PUTTING INTO OPERATION Page 8 SENSOR CALIBRATION Page 9 START UP DELAY AND PASSWORD Page 11 DETERMINATION OF THE REDOX CUT IN VALUES Page 12 PROGRAMMATION OF THE CUT IN VALUES...

Page 4: ...displayed during the calibration procedure The sensitivity range of the dosing station for the pH sensor is 46 to 72 mV pH with an amplification curve of 70 mV and 200 mVt for the Redox sensor ENTRY...

Page 5: ...n a distance of 50 cm from each other Use the adaptors provided for this purpose to attach the injector to the upper connection of the doser with the rigid tube opaque Tighten the fastening screw of t...

Page 6: ...ECTIONS POOL POOL POOL POOL POOL POOL FILTRATION CIRCUIT Fig 2 In the fitlter exit before and after heating or after booster pump PUMP FILTER HEATING BOOSTER PUMP INJECTIONS FILTRATION CIRCUIT Fig 3 I...

Page 7: ...OL PANEL CONNECTED TO 230 V CHLORINE pH CORRECTION Tank alarm sensor Lateral Water probe extraction with regulation valve POOL POOL INJECTIONS Probe extraction Analysis chamber Filter HEATING FILTER P...

Page 8: ...ates the quantity to be injected by the dosing pump The indicated value is proportional to the maximum flow rate The percentage below the Redox value indicates the proportional Redox regulation time c...

Page 9: ...keys the dosing station will remain in this mode until the power supply will discontinued The sensors must be calibrated during the installation procedure to obtain reliable measuring values Proceed...

Page 10: ...ding on the temperature and press ENTER to store the calibration If the calibration has been carried out correctly and if the sensor is in good condition the result will be displayed within a few seco...

Page 11: ...ain to go to screen 2 Select Parameter using the following key The following will be displayed Screen 5 Delay This value indicates how many minutes you have to wait until the dosing station will be st...

Page 12: ...w rate If the pH range is limited to 7 2 and 7 3 the dosing is still in the proportional mode but it approaches the ON OFF mode If approximately the same pH value is programmed the station works in th...

Page 13: ...e Complete with ENTER to save the data The SETPOINT SAVED message will appear on screen 6 Press ESC several times to quit and go back to screen 1 For your information 750mV at pH 7 3 equals to a value...

Page 14: ...ccess the terminal box The original value must be observed for the replacement of the fuse Start with the connection to earth We recommend that you install a differential circuit breaker sensitivity 3...

Reviews: