Procopi REGUL SYSTEM Instructions For Installation And Use Manual Download Page 13

13

Redox section (mV)

To start the programming in screen 1, press ENTER for 3 seconds, enter the password, if any,
press 

ENTER

, select Setup and press 

ENTER

again, select Set-Point,

press 

ENTER

and select mV:

ATTENTION :
IF NO KEY IS PRESSED FOR 90 SECONDS, THE DOSING STATION QUITS THE
PROGRAMMING MODE AND GOES BACK TO SCREEN 1.

Screen 6.2

If you press 

ENTER

, the following will be displayed:

Screen 6.3

The cursor indicates the values which can be modified. Use the 

# $

keys to modify the data.

You can switch to other areas pressing the 

! "

keys.

ln our example, screen 6.3 shows that the chlorine pump is stopped at a value of 700 mV or more.
If the mV value decreases (decreasing chlorine), the pump will be started and the proportional dosing
will be increased, until 100% of the maximum flow rate at 650 mV has been attained. Should the mV
value continue to decrease, the pump would continue to work a the maximum flow rate. Complete
with 

ENTER

to save the data. The "SETPOINT SAVED" message will appear on screen 6. Press

ESC

several times to quit and go back to screen 1.

For your information: 750mV at pH 7.3 equals to a value of 1.5 to 2 mg/l of free chlorine depending
on the water quality and conductivity.

ON/OFF mode (Option) :

You can enter OFF instead of 00 % and ON instead of 100 %, if you do not want to enter the
values in % (do not forget to reduce the range, for ex.: 690 = ON / 700 = OFF).

Set-Point

pH                     

%

mV

%

650  mV   =             100 %    

700  mV   =               00 % 

RECOMMENDATIONS

Only use the tubes delivered for the connection of the pumps.

The use of tubes other than

those delivered will cancel all guarantees.
- Suction tube (crystal type) and water return tube (opaque type) : 4 x 6 mm.
- Operating temperature: - 10 / + 60 °C.

If the regulation must be dismanteled to be transported, the doser tanks must be emptied to
avoid that any corrosive liquid escapes. Damage to the station due this will cancel all guarantees.

We recommend that you replace the cartridge of the circulaiton tank twice per year.

It is obligatory to connect the pool water entirely to earth, to avoid stray currents.

Summary of Contents for REGUL SYSTEM

Page 1: ...EM automatic dosing and regulation station This is an efficient powerful and reliable product Prior to installation and utilisation the subsequent information must be read carefully It contains import...

Page 2: ......

Page 3: ...ALLATION DIAGRAM Page 7 PUTTING INTO OPERATION Page 8 SENSOR CALIBRATION Page 9 START UP DELAY AND PASSWORD Page 11 DETERMINATION OF THE REDOX CUT IN VALUES Page 12 PROGRAMMATION OF THE CUT IN VALUES...

Page 4: ...displayed during the calibration procedure The sensitivity range of the dosing station for the pH sensor is 46 to 72 mV pH with an amplification curve of 70 mV and 200 mVt for the Redox sensor ENTRY...

Page 5: ...n a distance of 50 cm from each other Use the adaptors provided for this purpose to attach the injector to the upper connection of the doser with the rigid tube opaque Tighten the fastening screw of t...

Page 6: ...ECTIONS POOL POOL POOL POOL POOL POOL FILTRATION CIRCUIT Fig 2 In the fitlter exit before and after heating or after booster pump PUMP FILTER HEATING BOOSTER PUMP INJECTIONS FILTRATION CIRCUIT Fig 3 I...

Page 7: ...OL PANEL CONNECTED TO 230 V CHLORINE pH CORRECTION Tank alarm sensor Lateral Water probe extraction with regulation valve POOL POOL INJECTIONS Probe extraction Analysis chamber Filter HEATING FILTER P...

Page 8: ...ates the quantity to be injected by the dosing pump The indicated value is proportional to the maximum flow rate The percentage below the Redox value indicates the proportional Redox regulation time c...

Page 9: ...keys the dosing station will remain in this mode until the power supply will discontinued The sensors must be calibrated during the installation procedure to obtain reliable measuring values Proceed...

Page 10: ...ding on the temperature and press ENTER to store the calibration If the calibration has been carried out correctly and if the sensor is in good condition the result will be displayed within a few seco...

Page 11: ...ain to go to screen 2 Select Parameter using the following key The following will be displayed Screen 5 Delay This value indicates how many minutes you have to wait until the dosing station will be st...

Page 12: ...w rate If the pH range is limited to 7 2 and 7 3 the dosing is still in the proportional mode but it approaches the ON OFF mode If approximately the same pH value is programmed the station works in th...

Page 13: ...e Complete with ENTER to save the data The SETPOINT SAVED message will appear on screen 6 Press ESC several times to quit and go back to screen 1 For your information 750mV at pH 7 3 equals to a value...

Page 14: ...ccess the terminal box The original value must be observed for the replacement of the fuse Start with the connection to earth We recommend that you install a differential circuit breaker sensitivity 3...

Reviews: