12

PROGRAMMATION OF THE CUT-IN VALUES

The cut-in values are the threshold values of the dosing pump operation (“set points”).

pH section

Press E

NTER

for 3 seconds to enter the programming mode in the screen 1. Then enter the

password if any, press 

ENTER

, select Set up and press 

ENTER

again, select Set-Point,

press 

ENTER

, and select pH:

ATTENTION :
IF NO KEY IS PRESSED FOR 90 SECONDS, THE DOSING STATION QUITS THE
PROGRAMMING MODE AND GOES BACK TO SCREEN 1.

Screen 6    

If you press 

ENTER

, the following will be displayed:

Screen 6.1

The cursor indicates the values which can be modified. Use the 

# $

keys to modify the data.

You can switch to other areas pressing the 

! "

keys.

In our example, screen 6.1 shows that the acid dosing pump will be stopped at a pH value of 7.3
or less. If the pH value increases, the pump will be restarted and the flow rate will be adjusted
proportionally to reach 100% of the maximum flow rate at 7.8 pH. Should the pH value continue
to increase, the pump would continue to work at a maximum flow rate. If the pH range is limited
to 7.2 and 7.3, the dosing is still in the proportional mode, but it approaches the ON/OFF mode.
If approximately the same pH value is programmed, the station works in the ON/OFF mode.
Complete with 

ENTER

to save the data. The "SETPOINT SAVED" message will appear on th e

screen and the system will go back to screen 6. Press the 

ESC

key several times to go

back to screen 1.

ON/OFF mode (option) :

You can enter OFF instead of 00 % and ON instead of 100 %, if you do not want to enter the values
in % (do not forget to reduce the range, for example: 7.30 = OFF / 7.40 = ON).

Set-Point

pH 

&

mV

%

7.30 pH  =               00 %    

7.80 pH  =             100 % 

DETERMINATION OF THE REDOX CUT-IN VALUE

Proceed as follows to determine the Redox cut-in value:

- The pH value must be regulated to obtain the desired value (in general 7.2 - 7.4).
- Calibrate the sensor (see preceding chapter) and turn on the filter. 

The FRH pump must continue working.

- Manually add small doses of chlorine to the water. Use a reliable test kit (DPD) to analyse

the pool water after each chorine addition.

- When the analysis shows that the desired free chlorine values has been obtained,

the mV value displayed by the FRH pump must be recorded. Store this value as cut-in value.

Summary of Contents for REGUL SYSTEM

Page 1: ...EM automatic dosing and regulation station This is an efficient powerful and reliable product Prior to installation and utilisation the subsequent information must be read carefully It contains import...

Page 2: ......

Page 3: ...ALLATION DIAGRAM Page 7 PUTTING INTO OPERATION Page 8 SENSOR CALIBRATION Page 9 START UP DELAY AND PASSWORD Page 11 DETERMINATION OF THE REDOX CUT IN VALUES Page 12 PROGRAMMATION OF THE CUT IN VALUES...

Page 4: ...displayed during the calibration procedure The sensitivity range of the dosing station for the pH sensor is 46 to 72 mV pH with an amplification curve of 70 mV and 200 mVt for the Redox sensor ENTRY...

Page 5: ...n a distance of 50 cm from each other Use the adaptors provided for this purpose to attach the injector to the upper connection of the doser with the rigid tube opaque Tighten the fastening screw of t...

Page 6: ...ECTIONS POOL POOL POOL POOL POOL POOL FILTRATION CIRCUIT Fig 2 In the fitlter exit before and after heating or after booster pump PUMP FILTER HEATING BOOSTER PUMP INJECTIONS FILTRATION CIRCUIT Fig 3 I...

Page 7: ...OL PANEL CONNECTED TO 230 V CHLORINE pH CORRECTION Tank alarm sensor Lateral Water probe extraction with regulation valve POOL POOL INJECTIONS Probe extraction Analysis chamber Filter HEATING FILTER P...

Page 8: ...ates the quantity to be injected by the dosing pump The indicated value is proportional to the maximum flow rate The percentage below the Redox value indicates the proportional Redox regulation time c...

Page 9: ...keys the dosing station will remain in this mode until the power supply will discontinued The sensors must be calibrated during the installation procedure to obtain reliable measuring values Proceed...

Page 10: ...ding on the temperature and press ENTER to store the calibration If the calibration has been carried out correctly and if the sensor is in good condition the result will be displayed within a few seco...

Page 11: ...ain to go to screen 2 Select Parameter using the following key The following will be displayed Screen 5 Delay This value indicates how many minutes you have to wait until the dosing station will be st...

Page 12: ...w rate If the pH range is limited to 7 2 and 7 3 the dosing is still in the proportional mode but it approaches the ON OFF mode If approximately the same pH value is programmed the station works in th...

Page 13: ...e Complete with ENTER to save the data The SETPOINT SAVED message will appear on screen 6 Press ESC several times to quit and go back to screen 1 For your information 750mV at pH 7 3 equals to a value...

Page 14: ...ccess the terminal box The original value must be observed for the replacement of the fuse Start with the connection to earth We recommend that you install a differential circuit breaker sensitivity 3...

Reviews: