Chapter 3 - Installation and Wiring
GP-2300/2301 Series User Manual
3-3
• Be sure that the ambient operation temperature and the ambient
humidity are within their designated ranges. (When installing the GP
in a cabinet or enclosure, the term “ambient operation temperature”
indicates the cabinet or enclosure’s internal temperature.
• Be sure that heat from surrounding equipment does not cause the
GP to exceed its standard operating temperature.
• When installing the GP in a slanted panel, the panel face should not
incline more than 30
o
.
• When installing the GP in a slanted panel, and the panel face in-
clines more than 30
o
, the ambient temperature must not exceed 40
o
C. You may need to use forced air cooling (fan, A/C) to ensure the
ambient operating temperature is 40
o
C or below.
• When installing the GP vertically, position the unit so that the Power
Input Terminal Block is also vertical.
30
O
or less
Outside
Cabinet
Inside
Cabinet